Alloy 840 Sheathed Electric Duct Heaters, D Series, up to 225 kW
Duct heaters of the D series consist of tubular elements 11 mm in diameter mounted on a 6 mm steel flange. They are installed in ducts of air heating systems without excess pressure, with process temperatures from -29 to 650 °C. Catalogue ratings go up to 225 kW at supply voltages up to 600 V AC.
- Heating element diameter
- 11 mm (0.430 in)
- Flange thickness
- 6 mm (1/4 in)
- Power density
- up to 40 W/in² (6.2 W/cm²)
- Process temperature
- -20 to 1200 °F (-29 to 650 °C)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Heaters in this range are mounted straight into the duct through the flange. They suit many combinations of temperature and air flow in systems without excess pressure. Compared with gas or liquid-fuel units, an electric duct heater needs no chimney or fuel lines, and no heat is lost with flue gases. Compared with open coils, the resistance element here sits inside a sheath and is protected from corrosive surroundings.
The heating element has an alloy 840 sheath, and inside it the coil is insulated with magnesium oxide compacted to very high density. Surface power density reaches 40 W/in² (6.2 W/cm²), and the maximum sheath temperature is 760 °C. The elements rest on rigid stainless steel supports, and the silicone resin lead seals are rated to 105 °C. A thermowell with an inside diameter of 6 mm takes a temperature sensor, and the thermocouple leads are 3050 mm long.
Catalogue ratings reach 225 kW with a supply voltage up to 600 V AC, and the current per circuit does not exceed 48 A. The terminal box holds UL component recognition up to 480 V AC and CSA up to 600 V AC (files E52951 and 31388), and the enclosure temperature limit is 205 °C. The mounting holes in the flange are 9.5 mm in diameter.
Alongside the D series, the maker offers modular MDH duct heaters with 0.315 in elements in 6 kW modules and a maximum outlet air temperature of 399 °C. In that design, individual modules are withdrawn through the assembly housing without dismantling the whole heater, so single elements can be swapped and downtime shortened. The modular build also cuts response time and limits the ingress of airflow into the electrical box.
The heaters are built to NEC, UL and CSA requirements. When selecting one, you specify the power, supply voltage, number of circuits, process temperature and air flow in the duct.
Technical specifications
| Heating element diameter | 11 mm (0.430 in) |
|---|---|
| Flange thickness | 6 mm (1/4 in) |
| Power density | up to 40 W/in² (6.2 W/cm²) |
| Process temperature | -20 to 1200 °F (-29 to 650 °C) |
| Catalogue power | 225 kW maximum |
| Supply | 600 V AC maximum |
| Current per circuit | up to 48 A |
| Sheath material | alloy 840 |
| Insulation | compacted MgO |
| Maximum sheath temperature | 1400 °F (760 °C) |
| Lead seals | silicone resin, up to 221 °F (105 °C) |
| Thermowell | inside diameter 1/4 in (6 mm) |
| Thermocouple leads | 120 in (3050 mm) |
| Mounting holes | 3/8 in (9.5 mm) |
| Supports | stainless steel |
| Enclosure temperature limit | 400 °F (205 °C) |
| Recognition | UL to 480 V AC (E52951), CSA to 600 V AC (31388) |
Request a price and lead time
Alloy 840 Sheathed Electric Duct Heaters, D Series, up to 225 kW. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which systems is the D series suitable for?
Air heating systems without excess pressure, with different combinations of temperature and air flow. Process temperatures run from -29 to 650 °C.
What are the maximum power and voltage of the catalogue ratings?
Up to 225 kW at voltages up to 600 V AC, with a current of up to 48 A per circuit.
How does the MDH heater differ from the D series?
The MDH is built from 6 kW modules with 0.315 in elements, and the modules are withdrawn through the housing without dismantling the heater. Its outlet air temperature reaches 399 °C.
Similar equipment from other manufacturers