Series 531 backup PID control station for cooling water pumps, 1/4 DIN, 4-20 mA
Station 531 acts as a backup master controller on critical loops. It continuously monitors the 4-20 mA signal to the final control element and takes over PID control automatically if the primary pump PID controller fails.
- Type
- backup PID control station with hot standby
- Format
- 1/4 DIN
- Loop signal
- 4-20 mA
- Backup mode
- automatic PID takeover if the primary controller fails
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A typical use for the 531 is in data centres, where large volumes of cooling water circulate through server halls. Pumps are normally run by the building automation system, but continuous circulation during a control system failure needs an independent backup level. The same arrangement is used in oil and gas production and processing, power generation, chemical, pharmaceutical, pulp and paper, mining and food industries, water and effluent treatment, and semiconductor manufacturing.
In normal operation the station passes the 4-20 mA signal from the primary controller to the final element and monitors it continuously. If the primary pump PID controller fails, the 531 takes over the PID control at once, and the pump keeps running. At the same time the station sends a message to the primary controller or other supervisory systems, so that operations staff know the loop is running on the backup.
The instrument is a quarter-DIN panel-mount unit. A vacuum fluorescent display has a large five-digit upper line and two alphanumeric lines of nine characters each, with the process variable PV and control output CV shown in place. The enclosure meets NEMA 4X and the instrument carries UL approval. Setup is simple and is carried out on site.
The station is wired into the current loop between the primary pump controller and the final control element. Takeover is automatic and needs no operator action, so the flow of cooling water is not interrupted. The changeover message gives operations staff time to find and fix the fault in the primary controller while the loop runs from the 531.
Technical specifications
| Type | backup PID control station with hot standby |
|---|---|
| Format | 1/4 DIN |
| Loop signal | 4-20 mA |
| Backup mode | automatic PID takeover if the primary controller fails |
| Alerts | messages to primary controller or supervisory systems |
| Display | vacuum fluorescent |
| Indication | five-digit upper line, two lines of nine alphanumeric characters |
| Local indication | PV and CV |
| Enclosure | NEMA 4X |
| Approvals | UL |
Part numbers
Show all part numbers (1)
531
Request a price and lead time
Series 531 backup PID control station for cooling water pumps, 1/4 DIN, 4-20 mA. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What happens if the primary controller fails?
The 531 takes over the loop PID control at once, and the pump keeps running. The station also sends a message to the primary controller or the supervisory system.
Which signal does the station work with?
A 4-20 mA current signal, which in normal operation passes through the station to the final element.
Is the enclosure suitable for damp pump rooms?
The enclosure meets NEMA 4X and the instrument carries UL approval.