Porcelain station post insulators to IEC/ANSI for substations, BIL 60–2550 kV
PPC solid-core porcelain post insulators for substation switchyards and disconnectors of all voltage classes up to 1200 kV AC and 800 kV DC. The BIL insulation level is 60–2550 kV per IEC and 95–2050 kV per ANSI. Isostatic technology gives a column with fewer elements that is lower in height and lighter in weight.
- Insulation level BIL
- IEC: 60–2550 kV; ANSI: 95–2050 kV
- Standards
- IEC 60273, IEC 60815, ANSI C29.9
- Element length
- up to 2900 mm
- Body diameter
- 60–300 mm
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Isostatic pressing allows a single element up to 2900 mm long. Body diameter is 60–300 mm and shed diameter reaches 520 mm. The creepage distance is up to 55 mm/kV, and the shed profiles are designed to IEC 60815, including for 800 kV DC. The products comply with IEC 60273, IEC 60815 and ANSI C29.9. They serve as support insulation for busbars and disconnectors and as insulating operating rods for drives.
Technical specifications
| Insulation level BIL | IEC: 60–2550 kV; ANSI: 95–2050 kV |
|---|---|
| Standards | IEC 60273, IEC 60815, ANSI C29.9 |
| Element length | up to 2900 mm |
| Body diameter | 60–300 mm |
| Shed diameter | up to 520 mm |
| Creepage distance | up to 55 mm/kV |
| Technology | isostatic pressing; shed profiles per IEC 60815, including for 800 kV DC |
| Application | support insulation for busbars and disconnectors (including insulating operating rods for drives) |
Request a price and lead time
Porcelain station post insulators to IEC/ANSI for substations, BIL 60–2550 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8546 20 00 10 |
|---|---|
| HS, 6 digits | 8546 20 |
| CN (EU) | 8546 20 00 |
| HTSUS (USA) | 8546 20 00 30 |
| China customs tariff | 8546 20 90 90 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
What BIL range do PPC insulators cover?
Per IEC the insulation level is 60–2550 kV, per ANSI it is 95–2050 kV.
Which standards do the insulators comply with?
The insulators comply with IEC 60273, IEC 60815 and ANSI C29.9. Shed profiles are selected per IEC 60815.
Are the insulators suitable for direct current lines?
Yes, the insulators are applicable up to 800 kV DC, and separate shed profiles per IEC 60815 are available for this voltage.