KD2 (HV) — high-voltage flameproof motors Ex db / Ex db eb 3–11 kV, 180–1320 kW
KD2 in the high-voltage version is a series of three-phase squirrel-cage induction motors in a flameproof enclosure type d for gas Zone 1. Power 180–1320 kW, voltage 3–11 kV, shaft height 355–500 mm. The enclosure withstands an internal explosion and does not transmit it to the surrounding atmosphere.
- Series
- KD2 (high-voltage)
- Shaft height
- 355–500
- Power
- 180–1320 kW
- Voltage
- 3–11 kV (mains or VFD)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
KD2 motors are built at a plant in Mönchengladbach (Germany), which has belonged to an international industrial group since 2011. Marking II 2 G Ex db IIB or IIC T3/T4 Gb, or Ex db eb with an increased-safety terminal box. The flameproof enclosure is designed for an explosion inside and does not let it out.
Series parameters. Shaft height 355–500 mm, power 180–1320 kW, voltage 3–11 kV when supplied from the mains or a frequency converter, number of poles 2–16. Rolling or sleeve bearings, mounting arrangements B3, B35 and V1. Ribbed cast-iron frame with IC411 cooling. Degree of protection IP55, IP56 or IP65. Insulation class 155 (F) with use at class 130 (B).
The motors are ATEX certified, IECEx is possible. High-voltage flameproof motors are used in the oil and gas, chemical and petrochemical industries, at gas compressor and pump stations where type d protection is required in Zone 1. Under the same KD1/KD2 designation the manufacturer also makes low-voltage flameproof motors of 0.12–800 kW, which are listed as a separate item.
Among the manufacturer's machines for explosive atmospheres, its website lists, for example, the KR6031G-DC04 motor, 1000 kW, 6600 V, 1489 rpm, marked Ex db IIB T4 Gb. The series is considered an alternative to high-voltage flameproof motors of the ВАО2, 2В and АВ series; the final selection by application and parameters is agreed with a manager.
In the Ex db eb version the motor stays in a type d enclosure, while the terminal box has increased protection. For comparison, the KE2 increased-safety Ex eb series has a shaft height of 315–500 mm, and the KR series with IC511 tube cooling and a steel frame covers machines of much higher power. When selecting, specify the power, voltage, number of poles, gas group IIB or IIC and mounting arrangement. Mounting arrangements B3, B35 and V1 mean a horizontal foot-mounted motor, a foot-mounted motor with a flange, and a vertical motor.
Technical specifications
| Series | KD2 (high-voltage) |
|---|---|
| Shaft height | 355–500 |
| Power | 180–1320 kW |
| Voltage | 3–11 kV (mains or VFD) |
| Number of poles | 2–16 |
| Explosion protection | II 2 G Ex db IIB/IIC T3/T4 Gb or Ex db eb IIB/IIC T3/T4 Gb |
| Cooling | IC411 |
| Frame | cast iron |
| Bearings | rolling or sleeve |
| Degree of protection | IP55, IP56, IP65 |
| Insulation | 155 (F), use at 130 (B) |
| Mounting | B3, B35, V1 |
| Certification | ATEX, IECEx |
Request a price and lead time
KD2 (HV) — high-voltage flameproof motors Ex db / Ex db eb 3–11 kV, 180–1320 kW. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What explosion protection marking do high-voltage KD2 motors have?
II 2 G Ex db IIB or IIC T3/T4 Gb, as well as Ex db eb with an increased-safety terminal box. The series is intended for gas Zone 1.
What are the power and voltage of KD2 (HV) motors?
Power 180–1320 kW, voltage 3–11 kV, supplied from the mains or a frequency converter. Shaft height 355–500 mm, number of poles 2–16.
Where are high-voltage flameproof KD2 motors used?
In the oil and gas, chemical and petrochemical industries, at gas compressor and pump stations where type d protection is required in Zone 1. Degree of protection IP55, IP56 or IP65.