C73DL112 Loadbreak Type C Cutout and Surge Arrester on a Mount, 15 kV, 110 kV BIL
A pole-top pairing of a loadbreak Type C porcelain cutout and a distribution-class surge arrester, supplied factory-assembled on one mounting. Rated 15 kV and 110 kV BIL, it suits transformer and lateral protection on overhead distribution lines.
- Rated voltage
- 15 kV
- Maximum voltage
- 15 kV
- BIL
- 110 kV
- Current rating
- 100 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
On most distribution poles a cutout and an arrester end up side by side anyway. This combination puts both on a single mounting, so the line crew lifts and bolts one assembly and the interconnection is already made. The mounting assembly is non-interchangeable: the cutout and arrester are supplied and fitted as a set.
Arrester duty options listed by the manufacturer are standard, heavy and riser pole, all in the distribution class. Choose riser pole where the line drops to an underground cable.
The cutout half is a loadbreak design, meaning it is intended for opening under load. Ratings are 15 kV rated and maximum voltage, 110 kV BIL and 100 A continuous; in the C73DL112 group the fuse holder interrupts up to 10 kA. Its porcelain insulator offers 220 mm (8.7 in) of creepage. The holder accepts universal-style fuse links from 1 A to 100 A and is replaced with T730-112T. A single-vent solid cap closes the top and the bore is lined with synthetic arc-quenching material.
Catalogue numbers follow a simple pattern. C73DL112EB has a small eyebolt and the heavy-duty NEMA B crossarm bracket; C73DL112EX swaps in the extended NEMA B bracket; C73DL112LD pairs a large eyebolt with the D-shaped pole bracket. P in the connector position denotes a parallel-groove clamp. These items are listed as non-standard material.
The assembly complies with ANSI/IEEE C37.41 and C37.42 – 2016. Temperature rise at 300 A is capped at 39 °C and radio interference voltage is referenced to 9.41 kV.
Technical specifications
| Rated voltage | 15 kV |
|---|---|
| Maximum voltage | 15 kV |
| BIL | 110 kV |
| Current rating | 100 A |
| Fuse link range | 1 A to 100 A |
| Holder interrupting rating (C73DL112) | 10 kA |
| Creepage distance | 220 mm (8.7 in) |
| Max. temperature rise at 300 A | 39 °C |
| Radio interference voltage | at 9.41 kV |
| Insulator | porcelain |
| Replacement holder | T730-112T |
| Surge arrester | distribution class |
| Bracket | NEMA B, extended NEMA B, D-shape |
| Standard | ANSI/IEEE C37.41 & C37.42 – 2016 |
How it compares with similar models
| Parameter | C73DL112 Loadbreak Type C Cutout and Surge Arrester on a Mount, 15 kV, 110 kV BIL | C72DL112 Linkbreak Type C Cutout with Distribution Surge Arrester, 15 kV, 110 kV BIL | C730112 Loadbreak Type C Porcelain Cutout, 15 kV Class, 110 kV BIL, 100 A | C720112 Linkbreak Type C Porcelain Fuse Cutout, 15 kV, 110 kV BIL, 100 A |
|---|---|---|---|---|
| Max. temperature rise at 300 A | 39 °C | 38 °C | 39 °C | 38 °C |
| Replacement holder | T730-112T | T720-112T | T730-112T | T720-112T |
| Bracket | NEMA B, extended NEMA B, D-shape | NEMA B, extended NEMA B, D-shape | NEMA B, extended NEMA B, D-shape, none | NEMA B, extended NEMA B, D-shape, none |
Request a price and lead time
C73DL112 Loadbreak Type C Cutout and Surge Arrester on a Mount, 15 kV, 110 kV BIL. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the arrester be separated from the cutout and fitted elsewhere?
No. The mounting assembly is non-interchangeable, so the pair is installed as one unit; use separate devices if they must sit apart.
What replacement fuse holder does it need?
T730-112T for the C73DL112 group, rated 10 kA interrupting and taking universal links from 1 A to 100 A.
Which arrester duty ratings can be specified?
Standard, heavy and riser pole duty, all distribution class.
Similar equipment from other manufacturers