C730112 Loadbreak Type C Porcelain Cutout, 15 kV Class, 110 kV BIL, 100 A
A loadbreak Type C cutout with a porcelain body for 15 kV overhead distribution. Besides clearing overloads and faults on taps and transformers, it is intended to be opened under load during switching.
- Rated voltage
- 15 kV
- Maximum voltage
- 15 kV
- BIL
- 110 kV
- Current rating
- 100 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Weight is the first thing a crew notices on this one. C730112E without a bracket is 22.883 lb, C730112EB with the heavy-duty NEMA B crossarm bracket is 24.5 lb and C730112EX with the extended NEMA B bracket reaches 26.41 lb. A D-shaped pole bracket is also offered, and the connector letter in each catalogue number selects a small eyebolt (E), large eyebolt (L) or parallel-groove clamp (P).
Being a loadbreak design, it is meant to be opened under load, which matters on taps and transformer drops that cannot be offloaded first. The fuse link still does the protective work, melting on overload or short circuit and isolating the faulted section.
Ratings: 15 kV rated and maximum voltage, 110 kV BIL, 100 A continuous. Within the C730112 group the holder interrupts up to 10 kA and is replaced with T730-112T. Universal-style fuse links from 1 A to 100 A fit. The porcelain insulator gives 220 mm (8.7 in) of creepage.
Construction details include a single-vent solid cap, a synthetic arc-quenching liner in the holder and a non-interchangeable mounting assembly, so the unit is changed as a whole rather than moved onto another base.
Compliance is with ANSI/IEEE C37.41 and C37.42 – 2016. Temperature rise at 300 A stays within 39 °C, radio interference voltage is referenced to 9.41 kV and the minimum reference voltage limit extends to 14.4 kV.
Technical specifications
| Rated voltage | 15 kV |
|---|---|
| Maximum voltage | 15 kV |
| BIL | 110 kV |
| Current rating | 100 A |
| Fuse link range | 1 A to 100 A |
| Holder interrupting rating (C730112) | 10 kA |
| Creepage distance | 220 mm (8.7 in) |
| Max. temperature rise at 300 A | 39 °C |
| Radio interference voltage | at 9.41 kV |
| Insulator | porcelain |
| Replacement holder | T730-112T |
| Bracket | NEMA B, extended NEMA B, D-shape, none |
| Weight | 22.883 lb (C730112E), 24.5 lb (C730112EB), 26.41 lb (C730112EX) |
| Standard | ANSI/IEEE C37.41 & C37.42 – 2016 |
How it compares with similar models
| Parameter | C730112 Loadbreak Type C Porcelain Cutout, 15 kV Class, 110 kV BIL, 100 A | C720112 Linkbreak Type C Porcelain Fuse Cutout, 15 kV, 110 kV BIL, 100 A | C73DL112 Loadbreak Type C Cutout and Surge Arrester on a Mount, 15 kV, 110 kV BIL | C710112 / C710114 Type C Porcelain Fuse Cutout for 15 kV Overhead Lines, 110 kV BIL, 100 A |
|---|---|---|---|---|
| Max. temperature rise at 300 A | 39 °C | 38 °C | 39 °C | 38 °C |
| Replacement holder | T730-112T | T720-112T | T730-112T | — |
| Bracket | NEMA B, extended NEMA B, D-shape, none | NEMA B, extended NEMA B, D-shape, none | NEMA B, extended NEMA B, D-shape | NEMA B, extended NEMA B, D-shape, none |
Request a price and lead time
C730112 Loadbreak Type C Porcelain Cutout, 15 kV Class, 110 kV BIL, 100 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What does loadbreak mean for this cutout?
It is intended to be opened under load during switching. The electrical ratings remain 15 kV, 110 kV BIL and 100 A.
How heavy are the bracketed versions?
C730112EB with the NEMA B crossarm bracket weighs 24.5 lb; C730112EX with the extended bracket weighs 26.41 lb.
Which spares should be held?
T730-112T replacement holders, rated 10 kA, and universal-style fuse links between 1 A and 100 A.