C72DL112 Linkbreak Type C Cutout with Distribution Surge Arrester, 15 kV, 110 kV BIL
A Linkbreak Type C porcelain cutout and a distribution-class surge arrester delivered as one factory-built assembly. Intended for 15 kV overhead poles where a transformer or lateral needs both fault-current and overvoltage protection.
- Rated voltage
- 15 kV
- Maximum voltage
- 15 kV
- BIL
- 110 kV
- Current rating
- 100 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Three bracket choices cover most pole layouts. C72DL112EB comes with the heavy-duty NEMA B crossarm bracket, C72DL112EX with the extended NEMA B and C72DL112ED with a D-shaped bracket for direct pole mounting; all three use a small eyebolt connector, while large eyebolt (L) and parallel-groove (P) connectors are available in the range. Material is listed as non-standard.
The arrester sits on the same base as the cutout, already connected, and the mounting assembly is non-interchangeable, so the pair is fitted and replaced together. Arrester duty can be standard, heavy or riser pole, the last for poles where the line goes down to cable.
For the cutout itself the figures are 15 kV rated and maximum voltage, 110 kV BIL and 100 A continuous. The C72DL112 holder has a 10 kA interrupting rating and its spare is T720-112T. Fuse links are universal style, 1 A to 100 A. Creepage along the porcelain is 220 mm (8.7 in).
The holder is topped with a single-vent solid cap and lined with synthetic arc-quenching material.
The assembly complies with ANSI/IEEE C37.41 and C37.42 – 2016. Maximum temperature rise at 300 A is 38 °C, radio interference voltage is referenced to 9.41 kV and the minimum reference voltage limit is up to 14.4 kV.
Technical specifications
| Rated voltage | 15 kV |
|---|---|
| Maximum voltage | 15 kV |
| BIL | 110 kV |
| Current rating | 100 A |
| Fuse link range | 1 A to 100 A |
| Holder interrupting rating (C72DL112) | 10 kA |
| Creepage distance | 220 mm (8.7 in) |
| Max. temperature rise at 300 A | 38 °C |
| Radio interference voltage | at 9.41 kV |
| Insulator | porcelain |
| Replacement holder | T720-112T |
| Surge arrester | distribution class |
| Bracket | NEMA B, extended NEMA B, D-shape |
| Standard | ANSI/IEEE C37.41 & C37.42 – 2016 |
How it compares with similar models
| Parameter | C72DL112 Linkbreak Type C Cutout with Distribution Surge Arrester, 15 kV, 110 kV BIL | C73DL112 Loadbreak Type C Cutout and Surge Arrester on a Mount, 15 kV, 110 kV BIL | C720112 Linkbreak Type C Porcelain Fuse Cutout, 15 kV, 110 kV BIL, 100 A | C710112 / C710114 Type C Porcelain Fuse Cutout for 15 kV Overhead Lines, 110 kV BIL, 100 A |
|---|---|---|---|---|
| Max. temperature rise at 300 A | 38 °C | 39 °C | 38 °C | 38 °C |
| Replacement holder | T720-112T | T730-112T | T720-112T | — |
| Bracket | NEMA B, extended NEMA B, D-shape | NEMA B, extended NEMA B, D-shape | NEMA B, extended NEMA B, D-shape, none | NEMA B, extended NEMA B, D-shape, none |
Request a price and lead time
C72DL112 Linkbreak Type C Cutout with Distribution Surge Arrester, 15 kV, 110 kV BIL. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which spare holder suits the C72DL112 assembly?
T720-112T, rated 10 kA interrupting, taking universal fuse links from 1 A to 100 A.
Is there an arrester option for cable riser poles?
Yes, riser pole duty is listed alongside standard and heavy duty, all distribution class.
How do C72DL112EB, C72DL112EX and C72DL112ED differ?
By bracket only: heavy-duty NEMA B crossarm, extended NEMA B and D-shaped pole bracket, each with a small eyebolt connector.