C710112 / C710114 Type C Porcelain Fuse Cutout for 15 kV Overhead Lines, 110 kV BIL, 100 A
A conventional Type C distribution cutout with a porcelain body, rated 15 kV and 110 kV BIL. Fitted on overhead feeder taps and ahead of pole-mounted transformers, it drops a faulted section off the line once the fuse link operates.
- Rated voltage
- 15 kV
- Maximum voltage
- 15 kV
- BIL
- 110 kV
- Current rating
- 100 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Ordering is done by suffix. The C710112 and C710114 base numbers are followed by a connector letter (E for a small eyebolt, L for a large eyebolt, P for a parallel-groove clamp) and a bracket letter: B for the heavy-duty NEMA B crossarm bracket, X for the extended NEMA B version and D for the D-shaped bracket that bolts straight to the pole. Units without a bracket are also listed, and each catalogue number is marked as standard or non-standard material.
Electrically, the cutout is built for 15 kV distribution networks: rated and maximum voltage 15 kV, impulse level 110 kV BIL, continuous current 100 A. The porcelain body gives a creepage distance of 220 mm (8.7 in). The C710112 group carries a fuse holder with a 10 kA interrupting rating; its replacement holder is T710-112T.
Inside the holder sits a synthetic arc-quenching liner, and the top is a single-vent solid cap. Any universal-style fuse link from 1 A to 100 A can be used, so spares can be drawn from common stock.
Compliance is declared against ANSI/IEEE C37.41 and C37.42 – 2016. Temperature rise at 300 A is limited to 38 °C, radio interference voltage is referenced to 9.41 kV and the minimum reference voltage limit runs up to 14.4 kV.
For planning the pole top, note the weights: C710112EB with its crossarm bracket comes in at 18.434 lb, while C710112E with no bracket is 15.327 lb.
Technical specifications
| Rated voltage | 15 kV |
|---|---|
| Maximum voltage | 15 kV |
| BIL | 110 kV |
| Current rating | 100 A |
| Fuse link range | 1 A to 100 A |
| Holder interrupting rating (C710112) | 10 kA |
| Creepage distance | 220 mm (8.7 in) |
| Max. temperature rise at 300 A | 38 °C |
| Radio interference voltage | at 9.41 kV |
| Insulator | porcelain |
| Replacement holder (C710112) | T710-112T |
| Bracket | NEMA B, extended NEMA B, D-shape, none |
| Connector | small eyebolt, large eyebolt, parallel-groove |
| Standard | ANSI/IEEE C37.41 & C37.42 – 2016 |
| Weight C710112EB | 18.434 lb |
How it compares with similar models
| Parameter | C710112 / C710114 Type C Porcelain Fuse Cutout for 15 kV Overhead Lines, 110 kV BIL, 100 A | C720112 Linkbreak Type C Porcelain Fuse Cutout, 15 kV, 110 kV BIL, 100 A | C730112 Loadbreak Type C Porcelain Cutout, 15 kV Class, 110 kV BIL, 100 A | C72DL112 Linkbreak Type C Cutout with Distribution Surge Arrester, 15 kV, 110 kV BIL |
|---|---|---|---|---|
| Max. temperature rise at 300 A | 38 °C | 38 °C | 39 °C | 38 °C |
| Bracket | NEMA B, extended NEMA B, D-shape, none | NEMA B, extended NEMA B, D-shape, none | NEMA B, extended NEMA B, D-shape, none | NEMA B, extended NEMA B, D-shape |
Request a price and lead time
C710112 / C710114 Type C Porcelain Fuse Cutout for 15 kV Overhead Lines, 110 kV BIL, 100 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which fuse links does this cutout take?
Universal-style links from 1 A to 100 A. The cutout itself is rated 100 A continuous.
How do C710112EB, C710112ED and C710112EX differ?
Only in the bracket: B is the heavy-duty NEMA B crossarm bracket, D is the D-shaped pole bracket and X is the extended NEMA B. All three use the small eyebolt connector.
Which standards does the cutout comply with?
ANSI/IEEE C37.41 and C37.42 – 2016, at 15 kV and 110 kV BIL.