C720112 Linkbreak Type C Porcelain Fuse Cutout, 15 kV, 110 kV BIL, 100 A

A Linkbreak Type C distribution cutout with a porcelain insulator, rated 15 kV and 110 kV BIL. Used on overhead taps and transformer connections to isolate a section when its fuse link clears an overload or fault.

Rated voltage
15 kV
Maximum voltage
15 kV
BIL
110 kV
Current rating
100 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Spares are straightforward: the C720112 group takes the T720-112T replacement holder, rated 10 kA interrupting, and any universal-style fuse link from 1 A to 100 A. Keeping both on the van covers routine re-fusing after a fault.

In service the cutout sits on an overhead distribution pole. When its link melts on overload or short circuit, the faulted lateral or transformer is separated from the rest of the network. Ratings are 15 kV rated and maximum voltage, 110 kV BIL and 100 A continuous, with 220 mm (8.7 in) of creepage along the porcelain.

The bracket chosen changes the weight noticeably. C720112EB with the heavy-duty NEMA B crossarm bracket weighs 19.404 lb, C720112EX with the extended NEMA B bracket 21.61 lb and C720112ED with the D-shaped pole bracket 25.53 lb. These three have a small eyebolt connector; the range also lists large eyebolt (L) and parallel-groove (P) options, plus units without a bracket. Material is listed as non-standard.

The holder is closed by a single-vent solid cap and lined with synthetic arc-quenching material.

Compliance is with ANSI/IEEE C37.41 and C37.42 – 2016. Temperature rise at 300 A is limited to 38 °C, radio interference voltage is referenced to 9.41 kV and the minimum reference voltage limit is up to 14.4 kV.

Technical specifications

Rated voltage15 kV
Maximum voltage15 kV
BIL110 kV
Current rating100 A
Fuse link range1 A to 100 A
Holder interrupting rating (C720112)10 kA
Creepage distance220 mm (8.7 in)
Max. temperature rise at 300 A38 °C
Radio interference voltageat 9.41 kV
Insulatorporcelain
Replacement holderT720-112T
BracketNEMA B, extended NEMA B, D-shape, none
Weight19.404 lb (C720112EB), 21.61 lb (C720112EX), 25.53 lb (C720112ED)
StandardANSI/IEEE C37.41 & C37.42 – 2016

How it compares with similar models

ParameterC720112 Linkbreak Type C Porcelain Fuse Cutout, 15 kV, 110 kV BIL, 100 AC710112 / C710114 Type C Porcelain Fuse Cutout for 15 kV Overhead Lines, 110 kV BIL, 100 AC730112 Loadbreak Type C Porcelain Cutout, 15 kV Class, 110 kV BIL, 100 AC72DL112 Linkbreak Type C Cutout with Distribution Surge Arrester, 15 kV, 110 kV BIL
Max. temperature rise at 300 A38 °C38 °C39 °C38 °C
Replacement holderT720-112T—T730-112TT720-112T
BracketNEMA B, extended NEMA B, D-shape, noneNEMA B, extended NEMA B, D-shape, noneNEMA B, extended NEMA B, D-shape, noneNEMA B, extended NEMA B, D-shape

Request a price and lead time

C720112 Linkbreak Type C Porcelain Fuse Cutout, 15 kV, 110 kV BIL, 100 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What do the bracketed versions weigh?

C720112EB with the NEMA B bracket is 19.404 lb, C720112EX with the extended bracket 21.61 lb and C720112ED with the D-shaped bracket 25.53 lb.

Which fuse links can be used?

Universal-style links from 1 A to 100 A, in the T720-112T holder rated 10 kA.

What voltage class is the cutout for?

15 kV rated and maximum voltage, 110 kV BIL, 100 A continuous.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides