XMORE XMR-A, XMR-P — multifunction protection terminals for MV feeders and motors

XMR-A and XMR-P are multifunction intelligent devices of the XMORE platform for medium-voltage networks. They protect radial lines, transformers, motors and generators and also perform the functions of general protection (SPG) per CEI 0-16. XMR-P has up to 8 analog inputs.

Application
radial and ring lines, transformers, motors, generators; general protection (SPG) and interface protection (SPI) per CEI 0-16
Neutral
any mode: isolated, resistive, compensated, solidly earthed
Analog inputs
XMR-P up to 8, including from non-conventional CT/VT (ThySensor)
XMR-A current inputs
3 phases 1/5 A + Io 1/5 A (opt. second Io or Uo 50–130 V)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

XMORE is a complete line of IEDs for medium voltage, covering protection of feeders, motors, generators, transformers and capacitor banks. The hardware and software are modular, so both terminals scale in functions and performance. XMR-A works in distribution networks with any neutral earthing mode: isolated, earthed through a high- or low-resistance resistor, through an arc suppression reactor (compensated) or solidly earthed. It protects radial lines and transformers and also serves as a system of general protection (SPG) of active and passive consumers connected to the distribution network, certified to the Italian standard CEI 0-16. Directional earth fault protection 67N is added by an optional hardware pack.

The measuring circuits of XMR-A are as follows: three phase currents with a rated value of 1 or 5 A selected in software, and a zero-sequence current input of 1/5 A. A second Io input or a zero-sequence voltage input with a programmable rating of 50–130 V can optionally be added. XMR-P is an extended terminal for the same networks. It protects radial lines and transformers, performs SPG functions per CEI 0-16 with inputs from inductive CT/VT or from ThySensor sensors, and disconnects own generators from the distribution network upon loss of supply (Loss of Main). The version with ThySensor inputs is certified as an SPG with built-in interface protection SPI.

With an optional software pack the field of application extends to ring and long radial lines, generators and transformers operating in parallel (directional protections 67 and 67N), directional active and reactive power supervision, and multifunction protection of motors and generators. The functions include minimum impedance (21), overexcitation (24), directional power protections (32P, 32Q, 37P, 37Q), loss of excitation (40), negative sequence and machine thermal model (46MG, 49MG), locked rotor (51LR), start count limiting (66), rotor earth fault (64F), arc flash protection, rate of change of frequency (81R) and vector shift. XMR-P has up to 8 analog inputs, including inputs for non-conventional CT/VT, and power and energy metering with an accuracy class of up to 0.5.

Fault recording runs at 32 samples per cycle, and measurement for protections at 64 samples per cycle. For accurate recording of the sequence of events (SOE), time synchronization via PTP (IEC 1588) and SNTP is supported. Redundancy is provided by HSR, PRP and RSTP, and a built-in cybersecurity package is included. IEC 61850 Ed.1/Ed.2, IEC 60870-5-103, Modbus (serial and TCP) and DNP3 (serial and TCP) are supported; a DNV certificate confirms compliance of the IEC 61850 Ed.2 server for XMR-P, XMR-A, XMR-D, XMR-T and XMR-V. The terminals are installed in switchgear cubicles of distribution networks, at incomers of MV consumers, at industrial enterprises, and at renewable energy and oil and gas facilities.

Technical specifications

Applicationradial and ring lines, transformers, motors, generators; general protection (SPG) and interface protection (SPI) per CEI 0-16
Neutralany mode: isolated, resistive, compensated, solidly earthed
Analog inputsXMR-P up to 8, including from non-conventional CT/VT (ThySensor)
XMR-A current inputs3 phases 1/5 A + Io 1/5 A (opt. second Io or Uo 50–130 V)
Meteringaccuracy class up to 0.5
Functions67, 67N, 21, 24, 32P/Q, 37P/Q, 40, 46MG, 49MG, 51LR, 66, 64F, arc flash protection, 81R, vector shift
Fault recorder32 samples/cycle; measurement 64 samples/cycle
SynchronizationPTP (IEC 1588), SNTP
RedundancyHSR, PRP, RSTP
ProtocolsIEC 61850 Ed.1/Ed.2, IEC 60870-5-103, Modbus, DNP3

Request a price and lead time

XMORE XMR-A, XMR-P — multifunction protection terminals for MV feeders and motors. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which neutral earthing modes are XMR-A and XMR-P used with?

Any neutral earthing mode: isolated, earthed through a high- or low-resistance resistor, through an arc suppression reactor (compensated) and solidly earthed.

How many analog inputs does XMR-P have?

Up to 8, including inputs for non-conventional CT/VT. Power and energy metering is performed with an accuracy class of up to 0.5.

Are these terminals certified per CEI 0-16?

Yes, as a system of general protection SPG per CEI 0-16. The XMR-P version with ThySensor inputs is certified as an SPG with built-in interface protection SPI.