ВЛ-104, ВЛ-104А (VL-104, VL-104A) current time relays, three independent circuits, 0.1-9.9 s
The ВЛ-104 and ВЛ-104А (VL-104, VL-104A) give an adjustable time delay in AC-operated relay protection schemes. Three independent circuits, settings of 0.1-9.9 s in 0.1 s steps, rated current 5 A, connected straight into current transformer secondaries.
- Rated current in one or two phases
- 5 A
- AC frequency
- 50 Hz
- Minimum operating current (Imin)
- 2 A
- Output circuits with independent settings
- 3
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ВЛ-104 and ВЛ-104А (VL-104, VL-104A) are used in AC-operated relay protection schemes to obtain an adjustable time delay. They are connected directly into the secondary circuit of current transformers.
Each relay contains three independent output circuits with their own delay settings. Circuits 1 and 2 have a time-closing (sliding) contact, while circuit 3 has a closing (final) contact. The lower setting limit of circuit 1, T1, is 0.1 s; for circuit 2, T2 equals T1 + 0.5 s; for circuit 3, T3 equals T2 + 0.5 s. The upper limit for all three circuits is 9.9 s, so the delay range is 0.1-9.9 s, adjusted in steps of 0.1 s.
Rated current is 5 A in one or two phases at 50 Hz, with a minimum operating current (Imin) of 2 A. The sliding contacts stay closed for 0.4 ± 0.04 s and the repeat readiness time is up to 0.1 s. The continuous contact current is 5 A. Switching capacity is 30 W in DC circuits at τ ≥ 0.02 s and 400 VA in AC circuits at cosφ ≥ 0.4.
The relays are meant for closed industrial rooms in temperate and cold climates (version У3, U3). Operating temperature is -40 to 55 °C and relative humidity 80 %. Vibration is tolerated at up to 3g between 5 and 15 Hz and at 2g between 15 and 100 Hz.
Technical specifications
| Rated current in one or two phases | 5 A |
|---|---|
| AC frequency | 50 Hz |
| Minimum operating current (Imin) | 2 A |
| Output circuits with independent settings | 3 |
| Circuits with time-closing (sliding) contact | 1st and 2nd |
| Circuit with closing (final) contact | 3rd |
| Lower setting limits | T1 0.1 s; T2 T1 + 0.5 s; T3 T2 + 0.5 s |
| Upper setting limit of all circuits | 9.9 s |
| Adjustable delay range | 0.1 - 9.9 s |
| Adjustment step | 0.1 s |
| Adjustment method | stepped |
| Closed time of sliding contacts | 0.4 ± 0.04 s |
| Repeat readiness time | up to 0.1 s |
| Continuous contact current | 5 A |
| Switching capacity DC (τ ≥ 0.02 s) | 30 W |
| Switching capacity AC (cosφ ≥ 0.4) | 400 VA |
| Operating temperature | -40...+55 °С |
Part numbers
Show all part numbers (2)
ВЛ-104, ВЛ-104А
Request a price and lead time
ВЛ-104, ВЛ-104А (VL-104, VL-104A) current time relays, three independent circuits, 0.1-9.9 s. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Where is the ВЛ-104 connected?
Directly into the secondary circuit of current transformers in AC-operated relay protection schemes.
What settings do the three circuits have?
T1 starts at 0.1 s, T2 at T1 + 0.5 s and T3 at T2 + 0.5 s; all circuits end at 9.9 s, in steps of 0.1 s.
What is the minimum operating current?
The minimum operating current Imin is 2 A against a rated current of 5 A.