International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

ВЛ-103А (VL-103A) time relay with voltage monitoring, return delay 0.12-20 s

The ВЛ-103А (VL-103A) delays the return of its contacts after the supply is switched off or drops below a set value. It packs two relays into one, РН-54 and РВ-03 or РВ135. Pick-up is at 80 % Unom and the delay reaches 20 s, depending on the version.

Rated supply voltage
DC 110, 220 V; AC 50 Hz 100, 110, 220, 380 V
Pick-up voltage
80 % Unom
Return voltage
50 %...75 % Unom
Power consumption
up to 5 W (5 VA)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The ВЛ-103А (VL-103A) belongs in relay protection and system automation schemes, where it supplies a return time delay after the supply voltage is switched off or falls below a certain value. Two relays are combined in one housing: РН-54 and РВ-03 or РВ135.

The relay monitors its own supply voltage. It picks up at 80 % Unom and returns at 50 % to 75 % Unom. Rated AC voltage at 50 Hz is 100, 110, 220 or 380 V, and 110 and 220 V are listed for DC. Consumption is up to 5 W (5 VA).

There are two output circuits, one without a delay and one with an adjustable delay, and the contact set is one changeover and two normally open contacts. The delay setting range depends on the version: 0.12 to 5 s, 0.25 to 10 s or 0.5 to 20 s. Setting resolution is up to 2.5 % of the maximum setting of the range. Repeat readiness time is up to 0.3 s, the return time equals the setting on the scale, and mechanical endurance is at least 105 cycles.

The relay is intended for closed industrial rooms in temperate and cold climates (version У3, U3). Operating temperature is -40 to 55 °C at a relative humidity of 80 % at 25 °C. It tolerates vibration at up to 3g between 5 and 15 Hz and up to 2g between 15 and 100 Hz.

Technical specifications

Rated supply voltageDC 110, 220 V; AC 50 Hz 100, 110, 220, 380 V
Pick-up voltage80 % Unom
Return voltage50 %...75 % Unom
Power consumptionup to 5 W (5 VA)
Circuits without delay1
Circuits with adjustable delay1
Contacts1 changeover, 2 normally open
Delay range (by version)0.12-5; 0.25-10; 0.5-20 s
Setting resolutionup to 2.5 % of the maximum setting
Repeat readiness timeup to 0.3 s
Mechanical enduranceat least 105 cycles
Operating temperature-40...+55 °С

Part numbers

Show all part numbers (1)

ВЛ-103А

How it compares with similar models

ParameterВЛ-103А (VL-103A) time relay with voltage monitoring, return delay 0.12-20 sВЛ-100А, ВЛ-101А (VL-100A, VL-101A) three-circuit time relays with instant, sliding and final contactsВЛ-104, ВЛ-104А (VL-104, VL-104A) current time relays, three independent circuits, 0.1-9.9 sВЛ-81М (VL-81M) compact three-circuit time relay, 0.1 s - 99 h
Power consumptionup to 5 W (5 VA)6 VA (ВЛ-100А); 10 VA (ВЛ-101А)—up to 5 VA (W)
Repeat readiness timeup to 0.3 s0.1 s (ВЛ-100А); 0.1-0.3 s (ВЛ-101А)up to 0.1 s—

Request a price and lead time

ВЛ-103А (VL-103A) time relay with voltage monitoring, return delay 0.12-20 s. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What does the ВЛ-103А do?

It delays the return of its contacts after the supply is switched off or falls below a set value.

At what voltages does it pick up and return?

It picks up at 80 % Unom and returns at 50 % to 75 % Unom.

Which delay ranges exist?

Depending on the version: 0.12-5 s, 0.25-10 s or 0.5-20 s.