ВЛ-103А (VL-103A) time relay with voltage monitoring, return delay 0.12-20 s
The ВЛ-103А (VL-103A) delays the return of its contacts after the supply is switched off or drops below a set value. It packs two relays into one, РН-54 and РВ-03 or РВ135. Pick-up is at 80 % Unom and the delay reaches 20 s, depending on the version.
- Rated supply voltage
- DC 110, 220 V; AC 50 Hz 100, 110, 220, 380 V
- Pick-up voltage
- 80 % Unom
- Return voltage
- 50 %...75 % Unom
- Power consumption
- up to 5 W (5 VA)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ВЛ-103А (VL-103A) belongs in relay protection and system automation schemes, where it supplies a return time delay after the supply voltage is switched off or falls below a certain value. Two relays are combined in one housing: РН-54 and РВ-03 or РВ135.
The relay monitors its own supply voltage. It picks up at 80 % Unom and returns at 50 % to 75 % Unom. Rated AC voltage at 50 Hz is 100, 110, 220 or 380 V, and 110 and 220 V are listed for DC. Consumption is up to 5 W (5 VA).
There are two output circuits, one without a delay and one with an adjustable delay, and the contact set is one changeover and two normally open contacts. The delay setting range depends on the version: 0.12 to 5 s, 0.25 to 10 s or 0.5 to 20 s. Setting resolution is up to 2.5 % of the maximum setting of the range. Repeat readiness time is up to 0.3 s, the return time equals the setting on the scale, and mechanical endurance is at least 105 cycles.
The relay is intended for closed industrial rooms in temperate and cold climates (version У3, U3). Operating temperature is -40 to 55 °C at a relative humidity of 80 % at 25 °C. It tolerates vibration at up to 3g between 5 and 15 Hz and up to 2g between 15 and 100 Hz.
Technical specifications
| Rated supply voltage | DC 110, 220 V; AC 50 Hz 100, 110, 220, 380 V |
|---|---|
| Pick-up voltage | 80 % Unom |
| Return voltage | 50 %...75 % Unom |
| Power consumption | up to 5 W (5 VA) |
| Circuits without delay | 1 |
| Circuits with adjustable delay | 1 |
| Contacts | 1 changeover, 2 normally open |
| Delay range (by version) | 0.12-5; 0.25-10; 0.5-20 s |
| Setting resolution | up to 2.5 % of the maximum setting |
| Repeat readiness time | up to 0.3 s |
| Mechanical endurance | at least 105 cycles |
| Operating temperature | -40...+55 °С |
Part numbers
Show all part numbers (1)
ВЛ-103А
How it compares with similar models
| Parameter | ВЛ-103А (VL-103A) time relay with voltage monitoring, return delay 0.12-20 s | ВЛ-100А, ВЛ-101А (VL-100A, VL-101A) three-circuit time relays with instant, sliding and final contacts | ВЛ-104, ВЛ-104А (VL-104, VL-104A) current time relays, three independent circuits, 0.1-9.9 s | ВЛ-81М (VL-81M) compact three-circuit time relay, 0.1 s - 99 h |
|---|---|---|---|---|
| Power consumption | up to 5 W (5 VA) | 6 VA (ВЛ-100А); 10 VA (ВЛ-101А) | — | up to 5 VA (W) |
| Repeat readiness time | up to 0.3 s | 0.1 s (ВЛ-100А); 0.1-0.3 s (ВЛ-101А) | up to 0.1 s | — |
Request a price and lead time
ВЛ-103А (VL-103A) time relay with voltage monitoring, return delay 0.12-20 s. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What does the ВЛ-103А do?
It delays the return of its contacts after the supply is switched off or falls below a set value.
At what voltages does it pick up and return?
It picks up at 80 % Unom and returns at 50 % to 75 % Unom.
Which delay ranges exist?
Depending on the version: 0.12-5 s, 0.25-10 s or 0.5-20 s.