ВЛ-100А, ВЛ-101А (VL-100A, VL-101A) three-circuit time relays with instant, sliding and final contacts
The ВЛ-100А and ВЛ-101А (VL-100A, VL-101A) have three circuits with instant, sliding and final contacts. The ВЛ-100А times its delay after the supply is applied, the ВЛ-101А after it is removed. Contacts switch 24-250 V at 0.01-2 A.
- Number of circuits
- 3
- Contacts
- instant, sliding, final
- Supply voltage DC (ВЛ-100А)
- 24, 110, 115, 220, 230 V
- Supply voltage DC (ВЛ-101А)
- 110, 115, 220, 230 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ВЛ-100А and ВЛ-101А (VL-100A, VL-101A) switch electrical circuits with preset time delays in protection, emergency and industrial automation equipment. Each relay has three circuits fitted with an instant, a sliding and a final contact. The ВЛ-100А starts timing when the supply voltage is applied; the ВЛ-101А starts when it is removed.
Delays are adjusted in steps. Setting ranges of the ВЛ-100А are 0.05-4.95, 0.1-9.9, 0.3-29.7 and 1-99 s; the ВЛ-101А offers 0.05-4.95, 0.1-9.9 and 0.2-19.8 s. Repeat readiness time is 0.1 s for the ВЛ-100А and 0.1 to 0.3 s for the ВЛ-101А, and the ВЛ-100А returns in 0.08 s.
The ВЛ-100А runs from DC 24, 110, 115, 220, 230 V or AC 100, 220, 230, 380 V and consumes 6 VA. The ВЛ-101А runs from DC 110, 115, 220, 230 V or AC 100, 220, 230, 380 V and consumes 10 VA. The supply may deviate from 0.8 to 1.1 Unom.
Output contacts switch 24 to 250 V, DC or AC at 50 Hz, with a current of 0.01 to 2 A. Switching power is 300 VA on AC, and 60 W at τ = 0.05 s or 30 W at τ = 0.02 s on DC. Operating temperature range is -40 to +55 °C.
Mounting and connection dimensions are unified to make installation and servicing easier, and wires may be connected from either the front or the rear.
Technical specifications
| Number of circuits | 3 |
|---|---|
| Contacts | instant, sliding, final |
| Supply voltage DC (ВЛ-100А) | 24, 110, 115, 220, 230 V |
| Supply voltage DC (ВЛ-101А) | 110, 115, 220, 230 V |
| Supply voltage AC 50 Hz | 100, 220, 230, 380 V |
| Permitted supply voltage deviation | 0.8-1.1 Unom |
| Power consumption | 6 VA (ВЛ-100А); 10 VA (ВЛ-101А) |
| Setting ranges ВЛ-100А | 0.05-4.95; 0.1-9.9; 0.3-29.7; 1-99 s |
| Setting ranges ВЛ-101А | 0.05-4.95; 0.1-9.9; 0.2-19.8 s |
| Delay adjustment | stepped |
| Repeat readiness time | 0.1 s (ВЛ-100А); 0.1-0.3 s (ВЛ-101А) |
| Return time | 0.08 s (ВЛ-100А) |
| Switching voltage (DC and AC 50 Hz) | 24-250 V |
| Switching current | 0.01-2 A |
| Switching power AC | 300 VA |
| Switching power DC | 60 W (τ = 0.05 s); 30 W (τ = 0.02 s) |
| Operating temperature | -40...+55 °С |
Part numbers
Show all part numbers (2)
ВЛ-100А, ВЛ-101А
How it compares with similar models
| Parameter | ВЛ-100А, ВЛ-101А (VL-100A, VL-101A) three-circuit time relays with instant, sliding and final contacts | ВЛ-103А (VL-103A) time relay with voltage monitoring, return delay 0.12-20 s | ВЛ-81М (VL-81M) compact three-circuit time relay, 0.1 s - 99 h | ВЛ-104, ВЛ-104А (VL-104, VL-104A) current time relays, three independent circuits, 0.1-9.9 s |
|---|---|---|---|---|
| Power consumption | 6 VA (ВЛ-100А); 10 VA (ВЛ-101А) | up to 5 W (5 VA) | up to 5 VA (W) | — |
| Repeat readiness time | 0.1 s (ВЛ-100А); 0.1-0.3 s (ВЛ-101А) | up to 0.3 s | — | up to 0.1 s |
Request a price and lead time
ВЛ-100А, ВЛ-101А (VL-100A, VL-101A) three-circuit time relays with instant, sliding and final contacts. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the ВЛ-100А and ВЛ-101А differ?
The ВЛ-100А times its delay after the supply voltage is applied, the ВЛ-101А after it is removed.
Which setting ranges does the ВЛ-100А have?
0.05-4.95, 0.1-9.9, 0.3-29.7 and 1-99 s, adjusted in steps.
What voltage and current do the contacts switch?
24 to 250 V, DC or AC at 50 Hz, at 0.01 to 2 A.