UP — RTU for telecontrol of switching stations and MV transformer substations
UP is a microprocessor-based remote terminal unit for transformer substations and MV switching stations. It interacts with fault indicators and motor drives of switching devices. It is built to the ENEL DX1215 ed.5 specification.
- Inputs/outputs
- 8 (16) RGDAT ports, 8 (16) ports for motor-driven load-break switches, 8 (16) analog 4–20 mA, 8 (16) digital
- Supply
- 230/110 V AC with built-in charger
- Protocol
- IEC 60870-5-101 (PSTN, GSM, dedicated line)
- Specification
- ENEL DX1215 ed.5
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The RTU has 8 or 16 RGDAT ports, the same number of motor-driven load-break switch ports, 4–20 mA analog inputs and digital inputs. The supply is 230/110 V AC, and the charger is built in. Communication with the control centre runs over the IEC 60870-5-101 protocol via PSTN, GSM or a dedicated line. The RGDAT ports receive signals from directional fault indicators, and through the drive ports the RTU controls the cubicle load-break switches.
Technical specifications
| Inputs/outputs | 8 (16) RGDAT ports, 8 (16) ports for motor-driven load-break switches, 8 (16) analog 4–20 mA, 8 (16) digital |
|---|---|
| Supply | 230/110 V AC with built-in charger |
| Protocol | IEC 60870-5-101 (PSTN, GSM, dedicated line) |
| Specification | ENEL DX1215 ed.5 |
Request a price and lead time
UP — RTU for telecontrol of switching stations and MV transformer substations. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8537 10 98 90 |
|---|---|
| HS, 6 digits | 8537 10 |
| CN (EU) | 8537 10 98 |
| HTSUS (USA) | 8537 10 91 70 |
| China customs tariff | 8537 10 90 90 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
How many inputs and outputs does the UP RTU have?
8 or 16 each of RGDAT ports, load-break switch drive ports, 4–20 mA analog inputs and digital inputs.
Which communication protocol is used?
IEC 60870-5-101 via PSTN, GSM or a dedicated line.
What power supply does the RTU need?
230/110 V AC, and the charger is built in.
Similar equipment from other manufacturers