International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

TCA-A/C/D/E — RTUs with directional fault passage indicator for MV networks

TCA units are telecontrol terminals with a built-in directional fault current passage indicator for automation of secondary substations, RMUs and overhead line sectionalising points. They operate to IEC 60870-5-104 with FLISR, record 2500–4000 events and COMTRADE waveforms at 7200 Hz.

Versions
TCA-A — overhead lines and cables; TCA-C — compact RMUs with 2–3 feeders; TCA-D — load-break switches on overhead lines; TCA-E — modular switchgear and secondary substations
Neutral modes
solidly earthed, resistance-earthed, isolated, compensated (Petersen coil)
Protocol
IEC 60870-5-104 (FLISR)
Recording
2500–4000 events, COMTRADE waveforms 7200 Hz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The range is divided by the type of installation. TCA-A is fitted on overhead lines and cables, TCA-C on compact RMUs with 2–3 feeders, TCA-D on overhead line load-break switches, and TCA-E in modular switchgear and secondary substations. The indicator works in networks with solidly earthed neutral, resistance-earthed neutral, isolated neutral and compensated neutral with a Petersen coil. TCA-C has up to 48 DI, 8 DO and 14 analogue channels. Fault data and waveforms go to the dispatcher, and FLISR isolates the faulted section.

Technical specifications

VersionsTCA-A — overhead lines and cables; TCA-C — compact RMUs with 2–3 feeders; TCA-D — load-break switches on overhead lines; TCA-E — modular switchgear and secondary substations
Neutral modessolidly earthed, resistance-earthed, isolated, compensated (Petersen coil)
ProtocolIEC 60870-5-104 (FLISR)
Recording2500–4000 events, COMTRADE waveforms 7200 Hz
Inputs/outputsTCA-C — up to 48 DI, 8 DO, 14 analogue channels

Request a price and lead time

TCA-A/C/D/E — RTUs with directional fault passage indicator for MV networks. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8537 10 98 90
HS, 6 digits8537 10
CN (EU)8537 10 98
HTSUS (USA)8537 10 91 70
China customs tariff8537 10 90 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

Which TCA version should be chosen for an RMU?

TCA-C is intended for compact RMUs with 2–3 feeders, and TCA-E for modular switchgear and secondary substations.

For which neutral earthing modes does the indicator work?

For solidly earthed neutral, neutral earthed through a resistor, isolated neutral and compensated neutral with a Petersen coil.

How many events does TCA record and at what sampling rate?

2500–4000 events and COMTRADE waveforms at a sampling rate of 7200 Hz.