TCA-A/C/D/E — RTUs with directional fault passage indicator for MV networks
TCA units are telecontrol terminals with a built-in directional fault current passage indicator for automation of secondary substations, RMUs and overhead line sectionalising points. They operate to IEC 60870-5-104 with FLISR, record 2500–4000 events and COMTRADE waveforms at 7200 Hz.
- Versions
- TCA-A — overhead lines and cables; TCA-C — compact RMUs with 2–3 feeders; TCA-D — load-break switches on overhead lines; TCA-E — modular switchgear and secondary substations
- Neutral modes
- solidly earthed, resistance-earthed, isolated, compensated (Petersen coil)
- Protocol
- IEC 60870-5-104 (FLISR)
- Recording
- 2500–4000 events, COMTRADE waveforms 7200 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The range is divided by the type of installation. TCA-A is fitted on overhead lines and cables, TCA-C on compact RMUs with 2–3 feeders, TCA-D on overhead line load-break switches, and TCA-E in modular switchgear and secondary substations. The indicator works in networks with solidly earthed neutral, resistance-earthed neutral, isolated neutral and compensated neutral with a Petersen coil. TCA-C has up to 48 DI, 8 DO and 14 analogue channels. Fault data and waveforms go to the dispatcher, and FLISR isolates the faulted section.
Technical specifications
| Versions | TCA-A — overhead lines and cables; TCA-C — compact RMUs with 2–3 feeders; TCA-D — load-break switches on overhead lines; TCA-E — modular switchgear and secondary substations |
|---|---|
| Neutral modes | solidly earthed, resistance-earthed, isolated, compensated (Petersen coil) |
| Protocol | IEC 60870-5-104 (FLISR) |
| Recording | 2500–4000 events, COMTRADE waveforms 7200 Hz |
| Inputs/outputs | TCA-C — up to 48 DI, 8 DO, 14 analogue channels |
Request a price and lead time
TCA-A/C/D/E — RTUs with directional fault passage indicator for MV networks. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8537 10 98 90 |
|---|---|
| HS, 6 digits | 8537 10 |
| CN (EU) | 8537 10 98 |
| HTSUS (USA) | 8537 10 91 70 |
| China customs tariff | 8537 10 90 90 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
Which TCA version should be chosen for an RMU?
TCA-C is intended for compact RMUs with 2–3 feeders, and TCA-E for modular switchgear and secondary substations.
For which neutral earthing modes does the indicator work?
For solidly earthed neutral, neutral earthed through a resistor, isolated neutral and compensated neutral with a Petersen coil.
How many events does TCA record and at what sampling rate?
2500–4000 events and COMTRADE waveforms at a sampling rate of 7200 Hz.