International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

SPRECON-E-P DD6 — distance protection of MV/HV overhead lines and cables

SPRECON-E-P DD6 is a series of distance protection devices, the main protection of overhead lines and cables of medium and high voltage. The devices work in all common networks and in all neutral treatments, typically on 20–110 kV lines. As backup protection they also cover transformers and busbars.

Object
overhead lines and cables, MV and HV, any neutral treatment
Circuit breaker control
three-pole, three-phase auto-reclosing
Start
by current, by minimum impedance, by current with voltage supervision; 6 loops supervised
Additional functions
voltage/frequency protections, intermittent earth faults, Q-U<

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Several types of start are built in, with simultaneous impedance supervision of six measuring loops. In addition to starting by current and by minimum impedance, starting by current with voltage supervision is provided, so selectivity and sensitivity are maintained under any load. Circuit breaker control is three-pole, and tripping and closing are supplemented by three-phase auto-reclosing.

New functions are added to the proven protection and measurement algorithms. These are voltage and frequency protections, handling of intermittent earth faults and Q-U< protection. Accuracy is improved, there are many alarm and trip stages, and settings are grouped into 4 switchable sets. There are tools for testing and commissioning, selection of minimum relay hold time, combinational and sequential logic without programming (virtual binary inputs) and logic links for output relays. Circuit breaker control is optional, so the same device is used both as stand-alone protection and as protection with bay control.

The design is modular. A light flat detachable operator panel is built into the bay door, and a large full-graphic LCD clearly shows measurements and simplifies control and analysis. All operating actions and full protection setting on site are performed from the panel without the SPRECON-E COMM-3 program. The narrow housing of the protection device saves space in the relay compartment, and a layout in a medium housing is also available.

Alongside the protection-only SPRECON-E-P D..6-1 devices, combined DD..6-2 devices are produced, which protect equipment and at the same time perform control and monitoring. They are extended with modules for measuring transformers, analog inputs and outputs 0–20 mA, binary inputs and outputs, and a redundant power supply unit. The housings are medium and large, for 10 and 21 slots. The protection and control parts are strictly separated, with separate data models, firmware, parameterization and passwords. Therefore updating parameters or firmware of the control part does not require re-testing of the protection or switching off the bay.

The control part is built on a database with typification by identical bay types, which simplifies engineering of large systems. Standard and proprietary protocols are supported for communication with control systems of different manufacturers. Applications are 20–110 kV lines of distribution and transmission networks, cable networks of cities, and backup protection of transformers and busbars.

Technical specifications

Objectoverhead lines and cables, MV and HV, any neutral treatment
Circuit breaker controlthree-pole, three-phase auto-reclosing
Startby current, by minimum impedance, by current with voltage supervision; 6 loops supervised
Additional functionsvoltage/frequency protections, intermittent earth faults, Q-U<
Setting groups4
VersionsDD..6-1 (protection), DD..6-2 (combined, 10 or 21 slot housing)
Expansion modulesCT/VT, analog inputs/outputs 0–20 mA, binary, redundant power supply

Request a price and lead time

SPRECON-E-P DD6 — distance protection of MV/HV overhead lines and cables. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8537 10 98 00
HS, 6 digits8537 10
CN (EU)8537 10 98
HTSUS (USA)8537 10 91 70
China customs tariff8537 10 90 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

How many measuring loops does SPRECON-E-P DD6 supervise?

The device simultaneously supervises the impedance of 6 measuring loops. Starting is possible by current, by minimum impedance and by current with voltage supervision.

Does the device have auto-reclosing?

Yes, circuit breaker control is three-pole with three-phase auto-reclosing.

Which housings does the combined DD..6-2 version have?

Medium and large housings for 10 and 21 slots. They are extended with modules for measuring transformers, analog inputs and outputs 0–20 mA, binary signals and a redundant power supply.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides