SPRECON-E-EREG — arc suppression coil (Petersen coil) regulator

SPRECON-E-EREG is a regulator for arc suppression coils (Petersen coils) in medium voltage networks with a compensated neutral. It automatically tunes the coil in a healthy network in order to reduce damage at the fault location during an earth fault. The regulator is installed at 110/20 kV and 110/10 kV substations that feed cable and mixed 10–35 kV networks.

Purpose
automatic tuning of the arc suppression coil in compensated MV networks
Method
patented DiSpi method; detuning calculation without passing through the resonance point
Regulation
based on detuning and/or maximum permanent displacement voltage
Functions
multi-stage current injection, automatic phase selection, connection/disconnection of an external resistor

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Neutral treatment is among the main factors in the design of distribution networks. The most frequent type of fault statistically is a single-phase earth fault, and arc suppression in a compensated network maintains the power supply for the duration of such a fault. The arc suppression coil is tuned preventively, in the healthy network, and not after a fault occurs. The capacitive current of the network changes with every switching operation, so the coil tuning must be tracked continuously, and the regulator does this automatically.

The regulator reduces the number and duration of regulation processes and quickly detects detuning after switching operations. It determines the network parameters even in symmetrical networks with a very low neutral displacement voltage. Detuning shows how much the inductive current of the coil differs from the capacitive current of the network. Regulation is based on detuning and/or on the maximum permanent displacement voltage. The patented advanced DiSpi method improves response and tuning, and the current detuning is calculated without passing through the resonance point. In a symmetrical network the displacement voltage is low, so multi-stage current injection with automatic phase selection and connection and disconnection of an external resistor are provided for determining the parameters.

The regulator is part of the SPRECON platform, which gives several practical advantages. The security concept is consistent and meets the high requirements of critical infrastructure, with role-based access control RBAC, Syslog logging and digital certificates. Analysis covers statistical metrics and detailed records in COMTRADE format, so the behavior of the network during a fault can be analyzed after the event.

The regulator is fully digitally integrated into the substation control system. It is controlled remotely from the control center, including manual movement of the coil plunger. Service is performed through a web interface, and all measurements are flexibly processed by the control system together with other substation signals.

The regulator is complemented by the earth fault direction function SPRECON-EDIR and by SPRECON-E-P protections with intermittent fault handling. In this way a complete set for a compensated network is assembled on one platform, from coil tuning to locating the faulted feeder. The manufacturer publishes a description of the regulator as a separate document, E-Spulenregler (SPRECON-E-EREG). Applications are 110/20 kV and 110/10 kV substations with a compensated neutral, and cable and mixed 10–35 kV networks.

Technical specifications

Purposeautomatic tuning of the arc suppression coil in compensated MV networks
Methodpatented DiSpi method; detuning calculation without passing through the resonance point
Regulationbased on detuning and/or maximum permanent displacement voltage
Functionsmulti-stage current injection, automatic phase selection, connection/disconnection of an external resistor
SecurityRBAC, Syslog, digital certificates
Analysisstatistics, COMTRADE records
Integrationinto the substation control system, web interface, remote control from the control center

Request a price and lead time

SPRECON-E-EREG — arc suppression coil (Petersen coil) regulator. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)9032 89 00 00
HS, 6 digits9032 89
CN (EU)9032 89 00
HTSUS (USA)9032 89 60 90
China customs tariff9032 89 90 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

For which networks is SPRECON-E-EREG intended?

For medium voltage networks with a compensated neutral, typically cable and mixed 10–35 kV networks fed from 110/20 kV and 110/10 kV substations.

Does the regulator pass through the resonance point during tuning?

No, the patented DiSpi method calculates the current detuning without passing through the resonance point. Regulation is based on detuning and/or on the maximum permanent displacement voltage.

How is the regulator integrated into the substation control system?

Fully digitally, with remote control from the control center, a web interface and records in COMTRADE format. Access is protected through RBAC, Syslog and digital certificates.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides