SMO482-12 BMS bus signal converter with 12 relay outputs

The SMO482-12 turns serial BMS bus messages into relay contact signals. It has 12 output relays, an AC 230 V supply and an RS-485 interface. The contacts switch currents down to 5 mA.

Supply voltage Us
AC 230 V, 50…60 Hz
Operating range Us
0.8…1.15 x Us
Power consumption
≤ 8 VA
Outputs
12 x 1 N/O

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

A message arriving over the BMS bus (RS-485) from a connected device, such as an EDS or RCMS system, switches the output relay assigned to that channel. The SMO482-12 therefore passes alarm and operating messages to control circuits, disconnects faulty circuits selectively in EDS and RCMS installations and feeds data to central process and building control systems.

Messages from different BMS devices are assigned to individual relays. The settings must be made before first use, either at the factory (Option P, with a sticker on the unit listing the settings) or on site with a PC and the FTC470XET protocol converter. A BMS bus master is needed for operation. Each of the 12 channels has its own LED, and the TEST ON/OFF button puts the unit into test mode so the relays can be checked.

The bus address is the DIP switch value plus 30, with 30 + 1 set at the factory. The same switch changes the relays between N/O and N/C operation. The interface runs at 9.6 kbit/s over a cable of up to 1200 m, and a 120 Ω terminating resistor can be switched in with the DIP switch.

Contact rating is AC 250 V/DC 300 V with a minimum current of 5 mA, and the response time is below 100 ms. The unit meets the protective separation requirements of DIN EN 50178 up to 230 V. Supply is AC 230 V, 50…60 Hz at up to 8 VA.

The enclosure fits a DIN rail to IEC 60715, standard distribution panels to DIN 43871, or can be screw-mounted. It weighs 350 g, operates at -10…+55 °C and has a degree of protection of IP30/IP20. Installation, connection and commissioning are for qualified electricians only.

Technical specifications

Supply voltage UsAC 230 V, 50…60 Hz
Operating range Us0.8…1.15 x Us
Power consumption≤ 8 VA
Outputs12 x 1 N/O
Relay operating principleN/C or N/O, selected by DIP switch
Rated contact voltageAC 250 V/DC 300 V
Minimum current5 mA
Interface/protocolRS-485/BMS
Baud rate9.6 kbit/s
Cable length≤ 1200 m
Device address, BMS bus30 + (1…30)
InsulationAC 250 V; 4 kV/3
Operating temperature-10…+55 °C
Degree of protectionIP30/IP20
Weight350 g

Part numbers

Show all part numbers (2)

B95012039, B95012039P

How it compares with similar models

ParameterSMO482-12 BMS bus signal converter with 12 relay outputsSMI473 signal converter, 12 digital inputs to BMS bus, RS-485DI-1DL RS-485 interface repeater for BMS bus and Modbus RTUDI-2USB USB to RS-485 interface converter with galvanic separation
Supply voltage UsAC 230 V, 50…60 HzSMI473-12: DC 77…286 V/AC 85…265 V, 50…60 Hz; SMI473-1221: DC 12.5…80 VAC 85…260 V, 50…60 Hz—
Power consumption≤ 8 VA≤ 3 W0.1 A/7 W—
Interface/protocolRS-485/BMSRS-485/BMS2 x RS-485/BMS—
Baud rate9.6 kbit/s9.6… 57.6 kbit/sdynamic9.6…115.2 kbit/s
Operating temperature-10…+55 °C-10 … +55 °C0…+70 °C-10…+55 °C
Weight350 g≤ 320 gapprox. 90 g≤ 25 g

Request a price and lead time

SMO482-12 BMS bus signal converter with 12 relay outputs. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many outputs does the SMO482-12 have and how is their mode set?

It has 12 outputs, each with one N/O contact (12 x 1). N/C or N/O operation is selected with the DIP switch.

What is the device address on the BMS bus?

The address equals the DIP switch value plus 30, giving 30 + (1…30). The factory setting is 30 + 1.

Can it switch very small currents?

Yes, the contacts are suitable for currents from 5 mA. The rated contact voltage is AC 250 V/DC 300 V.