SMO482-12 BMS bus signal converter with 12 relay outputs
The SMO482-12 turns serial BMS bus messages into relay contact signals. It has 12 output relays, an AC 230 V supply and an RS-485 interface. The contacts switch currents down to 5 mA.
- Supply voltage Us
- AC 230 V, 50…60 Hz
- Operating range Us
- 0.8…1.15 x Us
- Power consumption
- ≤ 8 VA
- Outputs
- 12 x 1 N/O
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A message arriving over the BMS bus (RS-485) from a connected device, such as an EDS or RCMS system, switches the output relay assigned to that channel. The SMO482-12 therefore passes alarm and operating messages to control circuits, disconnects faulty circuits selectively in EDS and RCMS installations and feeds data to central process and building control systems.
Messages from different BMS devices are assigned to individual relays. The settings must be made before first use, either at the factory (Option P, with a sticker on the unit listing the settings) or on site with a PC and the FTC470XET protocol converter. A BMS bus master is needed for operation. Each of the 12 channels has its own LED, and the TEST ON/OFF button puts the unit into test mode so the relays can be checked.
The bus address is the DIP switch value plus 30, with 30 + 1 set at the factory. The same switch changes the relays between N/O and N/C operation. The interface runs at 9.6 kbit/s over a cable of up to 1200 m, and a 120 Ω terminating resistor can be switched in with the DIP switch.
Contact rating is AC 250 V/DC 300 V with a minimum current of 5 mA, and the response time is below 100 ms. The unit meets the protective separation requirements of DIN EN 50178 up to 230 V. Supply is AC 230 V, 50…60 Hz at up to 8 VA.
The enclosure fits a DIN rail to IEC 60715, standard distribution panels to DIN 43871, or can be screw-mounted. It weighs 350 g, operates at -10…+55 °C and has a degree of protection of IP30/IP20. Installation, connection and commissioning are for qualified electricians only.
Technical specifications
| Supply voltage Us | AC 230 V, 50…60 Hz |
|---|---|
| Operating range Us | 0.8…1.15 x Us |
| Power consumption | ≤ 8 VA |
| Outputs | 12 x 1 N/O |
| Relay operating principle | N/C or N/O, selected by DIP switch |
| Rated contact voltage | AC 250 V/DC 300 V |
| Minimum current | 5 mA |
| Interface/protocol | RS-485/BMS |
| Baud rate | 9.6 kbit/s |
| Cable length | ≤ 1200 m |
| Device address, BMS bus | 30 + (1…30) |
| Insulation | AC 250 V; 4 kV/3 |
| Operating temperature | -10…+55 °C |
| Degree of protection | IP30/IP20 |
| Weight | 350 g |
Part numbers
Show all part numbers (2)
B95012039, B95012039P
How it compares with similar models
| Parameter | SMO482-12 BMS bus signal converter with 12 relay outputs | SMI473 signal converter, 12 digital inputs to BMS bus, RS-485 | DI-1DL RS-485 interface repeater for BMS bus and Modbus RTU | DI-2USB USB to RS-485 interface converter with galvanic separation |
|---|---|---|---|---|
| Supply voltage Us | AC 230 V, 50…60 Hz | SMI473-12: DC 77…286 V/AC 85…265 V, 50…60 Hz; SMI473-1221: DC 12.5…80 V | AC 85…260 V, 50…60 Hz | — |
| Power consumption | ≤ 8 VA | ≤ 3 W | 0.1 A/7 W | — |
| Interface/protocol | RS-485/BMS | RS-485/BMS | 2 x RS-485/BMS | — |
| Baud rate | 9.6 kbit/s | 9.6… 57.6 kbit/s | dynamic | 9.6…115.2 kbit/s |
| Operating temperature | -10…+55 °C | -10 … +55 °C | 0…+70 °C | -10…+55 °C |
| Weight | 350 g | ≤ 320 g | approx. 90 g | ≤ 25 g |
Request a price and lead time
SMO482-12 BMS bus signal converter with 12 relay outputs. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many outputs does the SMO482-12 have and how is their mode set?
It has 12 outputs, each with one N/O contact (12 x 1). N/C or N/O operation is selected with the DIP switch.
What is the device address on the BMS bus?
The address equals the DIP switch value plus 30, giving 30 + (1…30). The factory setting is 30 + 1.
Can it switch very small currents?
Yes, the contacts are suitable for currents from 5 mA. The rated contact voltage is AC 250 V/DC 300 V.