International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

SIA-B self-powered overcurrent and earth fault relay for switchgear/RMUs

The compact SIA-B overcurrent and earth fault protection relay for secondary distribution cubicles and RMUs. It operates without auxiliary supply on the energy of the line CTs, with a self-powering threshold of 0.075·In for standard CTs.

Power supply
self-powered from CTs (standard /1 or special CTs) + opt. 24–230 V AC/DC, USB, power bank
Self-powering threshold
0.075·In (3 phases) for standard CTs; 0.4·In for special CTs
Functions
50/51, 50N/51N (50G/51G), opt. 46, 49, 50BF, 79, CLP
Trip output
to a 24 V DC trip coil – 135 mJ

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The supply is taken from standard CTs /1 or special CTs with a threshold of 0.4·In, optionally from 24–230 V AC/DC, USB or a power bank. The relay performs functions 50/51, 50N/51N (50G/51G), with optional 46, 49, 50BF, 79 and CLP. The trip output drives a 24 V DC trip coil with an energy of 135 mJ, communication is via USB, with optional RS485 (Modbus RTU / DNP3.0). The memory holds 1024 events, 20 fault reports and 10 COMTRADE waveforms. The relay is used at distribution substations, wind and solar plants.

Technical specifications

Power supplyself-powered from CTs (standard /1 or special CTs) + opt. 24–230 V AC/DC, USB, power bank
Self-powering threshold0.075·In (3 phases) for standard CTs; 0.4·In for special CTs
Functions50/51, 50N/51N (50G/51G), opt. 46, 49, 50BF, 79, CLP
Trip outputto a 24 V DC trip coil – 135 mJ
CommunicationUSB, opt. RS485 (Modbus RTU / DNP3.0)
Recording1024 events, 20 fault reports, 10 COMTRADE waveforms

Request a price and lead time

SIA-B self-powered overcurrent and earth fault relay for switchgear/RMUs. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8536 49 00 90
HS, 6 digits8536 49
CN (EU)8536 49 00
HTSUS (USA)8536 49 00 80
China customs tariff8536 49 00 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

Does the SIA-B relay need an auxiliary supply?

No, the relay is powered by the energy of the line CTs with a threshold of 0.075·In for standard CTs, and the 24–230 V AC/DC auxiliary supply is optional.

How does the relay trip the circuit breaker?

The trip output drives a 24 V DC trip coil with an energy of 135 mJ.

Where is SIA-B used?

In secondary distribution cubicles and RMUs at distribution substations, wind and solar plants.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides