MR-F-DOA4 Modbus RTU module with 4 relay outputs, 5 A per relay
The MR-F-DOA4 offers 4 changeover relay outputs for decentralised switching. A Modbus master controls it through standard registers over RS-485. Supply is 24 V AC/DC and it mounts on a TH35 rail.
- Operating voltage
- 24 V AC/DC +/- 10 % (SELV)
- Power consumption AC (max.)
- 80 mA
- Power consumption DC (max.)
- 40 mA
- Outputs
- 4 changeover contacts
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Decentralised switching tasks are the purpose of the MR-F-DOA4. It can switch motors, contactors, lamps, louvres and similar loads, provided the relay contacts are protected with measures suited to the load. A Modbus master, for example a COMTRAXX device, switches the outputs through standard registers.
Four relays with changeover contacts are fitted. Switching voltage is up to 250 V AC, continuous current is 5 A per relay, the total across all outputs is 12 A, and the switching frequency is 360 cycles per hour. The module needs 24 V AC/DC ±10 % (SELV) and draws up to 80 mA AC or 40 mA DC. It has polarity reversal protection for DC operation and protection against interchanged supply and bus connections.
The RS-485 interface runs Modbus RTU on a two-wire bus with potential equalisation, in bus or line topology, terminated with 120 Ω. Address (00 to 99), bit rate and parity are set with 2 rotary switches on the front or by software. The rate ranges from 1200 to 115200 Bd with 19200 Bd as the default. Parity defaults to Even (Odd and None are also available), and stop bits are 1 by default or 2.
The supply system is rated 230 / 400 V AC, with overvoltage category III | II, pollution degree 2|2, rated test voltage 4 kV | 4 kV and basic and reinforced insulation. Status is shown by green, red and yellow LEDs.
The housing measures 35 mm x 69.3 mm x 60 mm, weighs 95 g and clips onto a TH35 rail to IEC 60715 in any position. Terminals are push-in spring clamps. Up to 15 Modbus modules may sit side by side without a gap, or up to 2 A total consumption per supply connection. Operating temperature is -5 °C…55 °C, with IP40 for the housing and IP20 for the terminals.
Technical specifications
| Operating voltage | 24 V AC/DC +/- 10 % (SELV) |
|---|---|
| Power consumption AC (max.) | 80 mA |
| Power consumption DC (max.) | 40 mA |
| Outputs | 4 changeover contacts |
| Switching voltage relay output (max.) | 250 V AC |
| Continuous current relay output | 5 A / relay |
| Total current across all outputs | 12 A |
| Protocol | Modbus RTU, RS-485 |
| Address range | 00 - 99 |
| Transmission rate | min. 1200 Bit/s (Bd) to max. 115200 Bit/s (Bd) |
| Transmission rate default setting | 19200 Bit/s (Bd) |
| Rated test voltage | 4 kV | 4 kV |
| Dimensions | 35 mm x 69.3 mm x 60 mm |
| Weight | 95 g |
| Degree of protection | IP40 / IP20 |
| Operating temperature | -5 °C - 55 °C |
Part numbers
Show all part numbers (2)
BF25510010, 11083613210170
How it compares with similar models
| Parameter | MR-F-DOA4 Modbus RTU module with 4 relay outputs, 5 A per relay | MR-F-DI4 Modbus RTU module with 4 digital inputs, 24 V AC/DC | УСДМ-01 discrete data collection unit, 16 inputs, 8 relays, MODBUS RTU | DI-1DL RS-485 interface repeater for BMS bus and Modbus RTU |
|---|---|---|---|---|
| Weight | 95 g | 95 g | — | approx. 90 g |
| Operating temperature | -5 °C - 55 °C | -5 °C - 55 °C | — | 0…+70 °C |
Request a price and lead time
MR-F-DOA4 Modbus RTU module with 4 relay outputs, 5 A per relay. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What load can the MR-F-DOA4 outputs carry?
Up to 5 A per relay at up to 250 V AC, and up to 12 A in total across all outputs. The contacts should be protected to suit the load type.
How are the address and communication settings made?
With 2 rotary switches on the front or by software. The address is 00 to 99 and the bit rate is 1200 to 115200 Bd, defaulting to 19200 Bd.
How many modules can be mounted side by side?
Up to 15 Modbus modules in a row, or up to 2 A total consumption per supply connection. Beyond that a separate supply connection is needed.
Similar equipment from other manufacturers