International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

MICREX-VieW XX — monitoring and control system (DCS) for power plants and industrial facilities

MICREX-VieW XX is a distributed monitoring and control system (DCS) for small and medium-sized facilities, including power plants. The XCS-3000 Type E controller runs on the SX-Net network at 1 Gbit/s and refreshes data in 0.5 ms. The system supports up to 126 devices and up to 65,536 I/O points.

Composition
XCS-3000 control station, XOS-3000 operator station, XDS-3000 database station, XES-3000 engineering station, E-SX I/O remote input/output and IPU-II
Control network
SX-Net 1000 Mbit/s; star up to 3.2 km, ring up to 16 km; up to 126 stations (42 in a ring)
Data refresh
up to 0.5 ms
I/O network
E-SX bus 100 Mbit/s, up to 65,536 points

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

MICREX-VieW XX is a distributed monitoring and control system for small and medium-sized facilities. It is used to control process plants, electric drives and electrical equipment, including at power plants, metallurgical and chemical enterprises and in the water sector. The system scales from a compact single configuration to a fully redundant one, and the range includes a universal station combining operator and database functions.

The XCS-3000 control station performs both electrical equipment control and measurement and regulation functions in one controller. The operator station is designated XOS-3000. The XDS-3000 database station stores trends, alarms and the history of operator actions, and the engineering station is called XES-3000. The E-SX I/O remote input/output runs on a 100 Mbit/s bus, and an IPU-II module with redundancy is also available. The backbone control network complies with FL-net Ver.3, and the information network runs on Ethernet.

The XCS-3000 Type E controller is intended for high-speed control, for example of motors on metallurgical lines. The SX-Net network at 1 Gbit/s in a ring configuration keeps working if the ring is broken at a single point. The network length reaches 16 km (up to 3.2 km in a star), up to 126 devices can be connected, and according to the specification a ring allows 42 stations. Data is refreshed in packets within 0.5 ms, and multi-axis synchronization of the I/O of different controllers is provided. The source also states a scan cycle from 0.5 to 30 ms, synchronization between stations of ±1 µs and a clock range of 0.25–10 ms.

Program memory is 512 K steps, data memory is 2368 K words, and I/O is up to 65,536 points. Programming follows IEC 61131-3 (IL, ST, LD, FBD, SFC), with an instruction execution time of 0.006 µs.

A separate feature is continuity. The system connects to the manufacturer's previous networks (DPCS-F, PE-link, T-link) through network adapters and reuses the existing cabinets and application software, so modernization is carried out in stages and in a short time. The stated advantages are high clarity of presentation, integration with Windows programs, fast diagnostics, open interfaces and information protection. The system is complemented by the MICREX-NX DCS, the MICREX-VieW FOCUS system and the f(s)NISDAS data collection and analysis system.

Technical specifications

CompositionXCS-3000 control station, XOS-3000 operator station, XDS-3000 database station, XES-3000 engineering station, E-SX I/O remote input/output and IPU-II
Control networkSX-Net 1000 Mbit/s; star up to 3.2 km, ring up to 16 km; up to 126 stations (42 in a ring)
Data refreshup to 0.5 ms
I/O networkE-SX bus 100 Mbit/s, up to 65,536 points
XCS-3000 Type E controllerprogram memory 512 K steps, data memory 2368 K words; IEC 61131-3 (IL, ST, LD, FBD, SFC); 0.006 µs per instruction
Information/control LANEthernet; FL-net Ver.3
CompatibilityDPCS-F, PE-link, T-link; staged modernization of previous MICREX systems

Request a price and lead time

MICREX-VieW XX — monitoring and control system (DCS) for power plants and industrial facilities. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What are the speed and length of the control network in the XCS-3000 Type E?

The SX-Net network runs at 1 Gbit/s. The ring length reaches 16 km, a star up to 3.2 km, and up to 126 devices can be connected.

What are the controller memory size and programming languages?

Program memory is 512 K steps, data memory is 2368 K words, with up to 65,536 I/O points. The languages follow IEC 61131-3 (IL, ST, LD, FBD, SFC), and the instruction execution time is 0.006 µs.

Can the system be connected to the existing networks at the site?

Yes, network adapters allow connection to DPCS-F, PE-link and T-link. The existing cabinets and application software continue to be used, so modernization proceeds in stages.