LINETRAXX® PEM353 universal measuring device, class 0.5 S, Modbus RTU
The PEM353 records voltages, currents, power and energy in 2-, 3- and 4-wire systems, analyses harmonics up to the 31st and watches setpoints. Active energy accuracy is class 0.5 S, with RS-485 communication.
- Nominal system voltage
- 3(N) AC 230/400 V
- Current inputs I1, I2, I3
- 5 A / 1 A
- Current input I4
- 5 A (PEM353-N only)
- Digital outputs
- 2 relay outputs (PEM353, PEM353-N) or 2 solid-state pulse outputs (PEM353-P)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The LINETRAXX® PEM353 is a digital panel instrument for electrical quantities in 2-, 3- and 4-wire systems. It stands in for analogue indicating instruments and combines power quality monitoring, energy and power measurement with Time of Use, and limit value monitoring with setpoints and alarm forwarding. Harmonics are recorded up to the 31st order, together with THD.
Nominal system voltage is 3(N) AC 230/400 V, and the measuring voltage range is 10…828 V (up to 120 % Un) with an internal resistance above 12 MΩ on UL1-N, L2-N and L3-N. Current inputs I1, I2 and I3 take 5 A / 1 A over 0.1…200 % Inom at a burden below 0.15 VA, with an overload capacity of 2 x Inom continuously and 20 x Inom for up to 1 s. Active energy accuracy is class 0.5 S to IEC 62053-22.
Three versions exist. The PEM353 has two relay outputs and no I4 input, the PEM353-P has two solid-state pulse outputs (max. DC 30 V, 30 mA, cable up to 30 m) instead of relays, and the PEM353-N has two relay outputs and a 5 A I4 input for the N conductor. Only the PEM353-N includes data recorders. Relay contacts switch AC 250 V or DC 30 V at 5 A, and there are four galvanically isolated 24 V digital inputs.
Data leaves over RS-485 by Modbus RTU, BACnet MS/TP or DNP, with a cable length of up to 1200 m. The sequence of events log resolves 1 ms. The start page can be set to show 4 quantities on the large backlit graphic display.
Supply is AC/DC 95…250 V (±10 %), with a frequency range of DC, 47…440 Hz, and consumption under 5 VA. The measured frequency is 45…65 Hz. Fit it in a 92 mm x 92 mm panel opening; the front measures 96 x 96 mm. Window-type or split-core current transformers serve the current inputs. Conformity covers IEC 62053-22, IEC 60364-5-55, CE and UKCA.
Technical specifications
| Nominal system voltage | 3(N) AC 230/400 V |
|---|---|
| Current inputs I1, I2, I3 | 5 A / 1 A |
| Current input I4 | 5 A (PEM353-N only) |
| Digital outputs | 2 relay outputs (PEM353, PEM353-N) or 2 solid-state pulse outputs (PEM353-P) |
| Active energy accuracy class | 0.5 S acc. to IEC 62053-22 |
| Supply voltage | AC/DC 95…250 V (±10 %) |
| Supply frequency range | DC, 47…440 Hz |
| Power consumption | < 5 VA |
| Measuring voltage range | 10…828 V (max. 120 % Un) |
| Current measurement range | 0.1…200 % Inom |
| Overload capacity | 2 x Inom continuously, 20 x Inom ≤ 1 s |
| Relay contacts | AC 250 V or DC 30 V, 5 A |
| Digital inputs | 4, galvanically isolated, 24 V |
| Interface | RS-485, up to 1200 m |
| Protocols | Modbus RTU, BACnet MS/TP, DNP |
| Mounting opening | 92 mm x 92 mm |
| Device dimensions | 96 x 96 mm |
Part numbers
Show all part numbers (3)
B93100353, B93100354, B93100355
Request a price and lead time
LINETRAXX® PEM353 universal measuring device, class 0.5 S, Modbus RTU. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the PEM353, PEM353-P and PEM353-N differ?
The PEM353 has two relays, the PEM353-P two solid-state pulse outputs, and the PEM353-N two relays plus a 5 A I4 input and data recorders.
Which communication protocols does the PEM353 support?
Modbus RTU, BACnet MS/TP and DNP over RS-485, with a cable length of up to 1200 m.
What accuracy class applies to energy measurement?
Class 0.5 S to IEC 62053-22 for active energy.