ISOMETER® IRDH275BM-7 with AGH675S-7 coupling devices, insulation monitoring up to 15.5 kV
The IRDH275BM-7 main unit with AGH675S-7 coupling devices monitors insulation resistance in medium voltage IT systems up to AC/DC 15.5 kV. Response values 100 kΩ…10 MΩ, AMPPlus method, RS-485 (BMS) interface.
- Nominal voltage Un
- AC/DC 0…7.2 kV (AGH675S-7), AC/DC 0…15.5 kV (AGH675S-7MV15)
- Supply voltage Us
- AC 19.2…55 V / DC 19.2…72 V
- Cable length
- 2000 mm (AGH675S-7-2000), 500 mm (AGH675S-7-500, AGH675S-7MV15-500)
- Response values
- 100 kΩ…10 MΩ
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
This set pairs the IRDH275BM-7 main unit with an AGH675S-7 coupling device to monitor insulation resistance in medium voltage IT systems of AC, DC or AC/DC type. The AGH675S-7 covers AC/DC 0…7.2 kV and the AGH675S-7MV15 covers AC/DC 0…15.5 kV. It is intended for systems with galvanically connected rectifiers and converters, including drives with medium voltage converters.
The main unit uses the AMPPlus measuring method and adapts automatically to the system leakage capacitance. It offers two separately adjustable response values of 100 kΩ…10 MΩ, a 0(4)…20 mA current output, a history memory with real-time clock and a galvanically isolated RS-485 (BMS) interface. The monitored frequency range is 0…460 Hz.
The main unit is supplied with AC 19.2…55 V / DC 19.2…72 V. The coupling device is linked to it by cable: the AGH675S-7-2000 has a 2000 mm cable, while the AGH675S-7-500 and AGH675S-7MV15-500 have 500 mm. External kΩ measuring instruments can be connected to the system.
The IRDH275 main unit (220 x 280 x 83 mm) mounts on a DIN rail or with screws, and the AGH675S-7 measures 320 x 280 x 52 mm. A set consists of the main unit B91065120 and one coupling device: B913061, B913060 or B913058. The documents carry CE and UKCA marks and refer to IEC 61800-5-1:2003, IEC 60715 and EN 50110.
Technical specifications
| Nominal voltage Un | AC/DC 0…7.2 kV (AGH675S-7), AC/DC 0…15.5 kV (AGH675S-7MV15) |
|---|---|
| Supply voltage Us | AC 19.2…55 V / DC 19.2…72 V |
| Cable length | 2000 mm (AGH675S-7-2000), 500 mm (AGH675S-7-500, AGH675S-7MV15-500) |
| Response values | 100 kΩ…10 MΩ |
| Frequency | 0…460 Hz |
| Current output | 0(4)…20 mA |
| Interface | RS-485 (BMS) |
| Mounting | DIN rail, screw mounting |
| Dimensions IRDH275 | 220 x 280 x 83 mm |
| Dimensions AGH675S-7 | 320 x 280 x 52 mm |
Part numbers
Show all part numbers (5)
B91065120 (main unit), B913061, B913060, B913058, B986849
How it compares with similar models
| Parameter | ISOMETER® IRDH275BM-7 with AGH675S-7 coupling devices, insulation monitoring up to 15.5 kV | ISOMETER® isoCHA425HV with coupling device AGH420-1/AGH421-1 for CCS and CHAdeMO DC charging stations | ISOMETER® isoES425 insulation monitoring device for storage up to AC/DC 400 V | ISOMETER® isoGEN423 insulation monitoring device for mobile generators up to 3(N)AC, AC/DC 400 V |
|---|---|---|---|---|
| Supply voltage Us | AC 19.2…55 V / DC 19.2…72 V | — | AC 100…240 V / DC 24…240 V | AC 100…240 V / DC 24…240 V |
| Interface | RS-485 (BMS) | Modbus RTU (RS-485) | RS-485 (BMS, isoData, Modbus RTU) | — |
Request a price and lead time
ISOMETER® IRDH275BM-7 with AGH675S-7 coupling devices, insulation monitoring up to 15.5 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What system voltage does the set cover?
Up to AC/DC 7.2 kV with the AGH675S-7 and up to AC/DC 15.5 kV with the AGH675S-7MV15.
What cable lengths do the coupling devices have?
2000 mm for the AGH675S-7-2000 and 500 mm for the AGH675S-7-500 and AGH675S-7MV15-500.
What response values and interface are provided?
Two separate response values of 100 kΩ…10 MΩ, a galvanically isolated RS-485 (BMS) interface and a 0(4)…20 mA current output.