International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

HIPASE-S and SYN 3000: automatic precise synchronizing devices for generators and grids

HIPASE-S is an automatic precise synchronizing device for generators, motors, synchronous condensers, lines and grids for 2 or 7 breakers. It measures one or three phases and works at 50 and 60 Hz, and a separate 7-breaker version is intended for 16.7 Hz railway grids. The previous generation is represented by the SYN 3000 synchronizer with five operating modes.

HIPASE-S versions
2 or 7 breakers, single-phase or three-phase measurement, 50/60 Hz; 7 breakers for railway (16.7 Hz)
Supply
24-250 V DC
Angle limits
1-30 °el. generator/grid; 1-80 °el. grid/grid; 1-10 °el. SFC/grid
Frequency limits
0.01-0.5 Hz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Synchronizing a rotating machine with a grid, or two grids with each other, does not forgive mistakes, and as the demands on power system flexibility grow it must be done quickly even in difficult conditions. The manufacturer has worked in this field for more than 50 years and has a large installed base of synchronizers. HIPASE-S connects in parallel grids, loaded and unloaded lines, generators, pump motors and synchronous condensers, that is, it covers all kinds of generation. Frequency matching in all variants shortens synchronizing time and reduces mechanical loads at the moment of closing.

A full-graphic touch panel shows all process parameters and helps select synchronizing setpoints during testing and commissioning. The event log and a high-resolution analyzer with multi-stage automatic curve recording store a detailed history of the last 100 synchronizations. The supply is 24-250 V DC, the rated frequency 50/60/16.7 Hz. The angle limits are 1-30 °el. for a generator/grid pair, 1-80 °el. for grid/grid and 1-10 °el. for SFC/grid, and the frequency limits are 0.01-0.5 Hz. Binary outputs switch 250 V AC or 230 V DC at a current of up to 8 A. The device measures the breaker closing time in the range 10-1 000 ms and stores it as a parameter.

The synchronizer can be combined with protection in one device, HIPASE-PS. The whole HIPASE line runs on a single hardware platform and firmware and is programmed with one tool, HIPASE Engineering Tool, in the form of function block diagrams per IEC 61131. The housing has half or full 19″ width, and a 7″ color touch panel can be built-in or separate. The device supports IEC 61850 (MMS, GOOSE), IEC 60870-5-103/-104, Modbus TCP, OPC UA and FTP. Cybersecurity is provided by separate application and communication processors, a firewall, encryption and regular updates.

SYN 3000 has five modes: generator with a system or a line, synchronous and asynchronous systems, closing onto a dead bus, synchro-check at manual closing, and control of busbar automatic transfer. It measures and stores the breaker closing time, the voltage measuring circuits are dual, and a 2-channel version is available for the highest requirements. The SYN-WIN program shows the process online on a computer screen with a dual voltmeter, a dual frequency meter and a synchroscope. Synchronizers are installed at hydropower plants, thermal power plants, pumped-storage plants, substations and power system tie points.

Technical specifications

HIPASE-S versions2 or 7 breakers, single-phase or three-phase measurement, 50/60 Hz; 7 breakers for railway (16.7 Hz)
Supply24-250 V DC
Angle limits1-30 °el. generator/grid; 1-80 °el. grid/grid; 1-10 °el. SFC/grid
Frequency limits0.01-0.5 Hz
Breaker closing time measurement10-1 000 ms
Archivehistory of the last 100 synchronizations with waveforms
ProtocolsIEC 60870-5-104, Modbus TCP
SYN 30005 modes, 2-channel version, SYN-WIN software

Request a price and lead time

HIPASE-S and SYN 3000: automatic precise synchronizing devices for generators and grids. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many breakers does HIPASE-S serve?

The device is made for 2 or 7 breakers with single-phase or three-phase measurement for 50 or 60 Hz. For 16.7 Hz railway grids there is a separate 7-breaker version.

What are the synchronizing limits for angle and frequency?

For angle, 1-30 °el. for a generator with a grid, 1-80 °el. for two grids and 1-10 °el. for SFC with a grid. The frequency limits are set in the range 0.01-0.5 Hz.

Can the synchronizer be combined with protection in one device?

Yes, in the HIPASE-PS version synchronizing and protection work in one device. Both functions are configured with one tool, HIPASE Engineering Tool.