EXmux 3505 IP Access Multiplexer for Substations, 3RU or 5RU Chassis
The eXmux 3505 carries voice, serial data, teleprotection, SCADA, video and Ethernet traffic over Ethernet/IP or MPLS networks. It combines legacy DS0 and T1/E1 interfaces with Ethernet equipment on one platform, and it is offered with hot-swappable modules or in a compact chassis.
- Type
- IP access multiplexer, substation version
- Networks
- Ethernet/IP, MPLS
- Throughput
- Gigabit Ethernet, 10 Gigabit Ethernet
- Interfaces
- RS-232, RS-485, RS-422/RS-530, V.35, X.21, G.703, C37.94, teleprotection, 2W and 4W E&M, 2W FXO, 2W FXS, T1/E1
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The multiplexer is designed for substations and for critical infrastructure such as electricity networks, transport, telemetry and protection systems. A single Ethernet/IP or MPLS network carries telephone channels, RS-232, RS-485, RS-422/RS-530, V.35, X.21, G.703, C37.94, teleprotection signals, 2W and 4W E&M, 2W FXO, 2W FXS and T1/E1 streams. Legacy equipment and new Ethernet devices can therefore run on the same platform.
The chassis is offered in two forms. The version for critical applications is a 19 inch 5RU chassis in which all interface modules, power supplies and the switch can be replaced in the field on a live unit within seconds. The compact model is 3RU high and suits locations where hot swapping is not needed. The 3505 and 3501 models operate on the same network and are physically interchangeable.
The chassis takes up to 7 DS0 or T1/E1 interface modules, and a standard T1/E1 interface and a two-wire service telephone channel are also provided. The built-in DACS function switches individual DS0 channels between T1/E1 streams, eXmux 3505 interfaces or another TDM network. Configuration, port allocation, maintenance and remote firmware upgrades are carried out with the VNMS network management software.
For private ring networks the Hitless Switching function restores the path without data loss, while public networks can use dual-path transmission with backup routes. The built-in end-to-end teleprotection carries 4 bidirectional trip commands, has 2 control inputs and 2 outputs for alarm and status, and on intermediate sections is compatible with the MTS system of the IMUX 2000 T1/E1 multiplexer. The minimum delay is designed for SCADA/RTU, protection relaying and real-time teleprotection.
Cyber security is provided through SNMPv3 with authentication and encryption, together with a built-in user access control system, and the feature set meets NERC requirements. Throughput covers Gigabit Ethernet and 10 Gigabit Ethernet. The unit is cooled by convection without fans and operates between -30 and +65 °C. Power input can be 38–150 VDC/88–130 VAC, 200–300 VDC/200–275 VAC or 19–32 VDC. It complies with ANSI C37.94, IEEE P1613, IEC 61850-3, ANSI C37.90.2 and ANSI C37.90.3.
Technical specifications
| Type | IP access multiplexer, substation version |
|---|---|
| Networks | Ethernet/IP, MPLS |
| Throughput | Gigabit Ethernet, 10 Gigabit Ethernet |
| Interfaces | RS-232, RS-485, RS-422/RS-530, V.35, X.21, G.703, C37.94, teleprotection, 2W and 4W E&M, 2W FXO, 2W FXS, T1/E1 |
| Interface modules | up to 7 DS0 or T1/E1, standard T1/E1, service telephone channel |
| Chassis | 19 inch, 5RU with hot swap or 3RU compact |
| Height / width / depth | 5.25 in / 19 in / 11 in |
| Teleprotection | 4 bidirectional commands, 2 inputs, 2 outputs |
| Operating temperature | -30 to +65 °C |
| Power supply | 38–150 VDC/88–130 VAC, 200–300 VDC/200–275 VAC, 19–32 VDC |
| Cooling | convection, no fans |
| Cyber security | SNMPv3, user access control |
| Standards | ANSI C37.94, IEEE P1613, IEC 61850-3, ANSI C37.90.2, ANSI C37.90.3 |
| Models | eXmux 3505, eXmux 3501 |
Request a price and lead time
EXmux 3505 IP Access Multiplexer for Substations, 3RU or 5RU Chassis. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the eXmux 3505 be combined with existing eXmux 3501 units?
Yes. The 3505 and 3501 models operate on the same network and are physically interchangeable.
Which legacy interfaces does the multiplexer support?
RS-232, RS-485, RS-422/RS-530, V.35, X.21, G.703, C37.94, E&M, FXO, FXS and T1/E1. The chassis takes up to 7 DS0 or T1/E1 interface modules.
How does the 5RU chassis differ from the 3RU chassis?
In the 5RU chassis all modules, power supplies and the switch can be replaced on a live unit. The compact 3RU chassis does not offer hot swapping of modules.
Similar equipment from other manufacturers