DBF / DBN (DBC, DBP, DRV, DCV) distributed busbar differential protection

DBF and DBN are a busbar differential protection system made of a central unit and bay units for substations with any busbar layout, including digital ones. DBF covers up to 24 bays and 4 busbar systems, DBN up to 28-32 bays and 5 busbar systems, using low-impedance differential protection together with breaker failure protection.

Scope
DBF: up to 24 bays and 4 busbar systems; DBN: up to 28-32 bays and 5 busbar systems
Principle
low-impedance differential protection + breaker failure protection
Central unit to bay link
optical fibre; DBF: process bus IEC 61869-9, GOOSE, PRP/HSR
Cybersecurity
IEC 62351, IEC 62443, IEEE 1686

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Bay units are installed near the cells and connected to the central unit by optical fibre, so copper cables from each CT to a single cabinet are not needed. In DBF, communication can run over a process bus per IEC 61869-9 with GOOSE messages and PRP/HSR redundancy, which suits a digital substation. The central unit determines on which busbar system the fault occurred and trips only its bays. The breaker failure function trips the adjacent breakers if the breaker of the faulted bay has not operated. Cybersecurity is implemented per IEC 62351, IEC 62443 and IEEE 1686.

Technical specifications

ScopeDBF: up to 24 bays and 4 busbar systems; DBN: up to 28-32 bays and 5 busbar systems
Principlelow-impedance differential protection + breaker failure protection
Central unit to bay linkoptical fibre; DBF: process bus IEC 61869-9, GOOSE, PRP/HSR
CybersecurityIEC 62351, IEC 62443, IEEE 1686

Request a price and lead time

DBF / DBN (DBC, DBP, DRV, DCV) distributed busbar differential protection. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8536 49 00 90
HS, 6 digits8536 49
CN (EU)8536 49 00
HTSUS (USA)8536 49 00 80
China customs tariff8536 49 00 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

How many bays and busbar systems does the protection cover?

DBF covers up to 24 bays and 4 busbar systems, DBN up to 28-32 bays and 5 busbar systems.

Does the system work in a digital substation?

Yes, DBF supports a process bus per IEC 61869-9, GOOSE and PRP/HSR redundancy.

Which cybersecurity requirements does the system meet?

Compliance with IEC 62351, IEC 62443 and IEEE 1686 is declared.