International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

SEL-421 / SEL-311C / SEL-9L — distance protection for power lines

Distance and directional protection, automation and control terminals for power lines SEL-421, SEL-311C and SEL-9L, with up to 5 distance protection zones using mho and quadrilateral characteristics. Current inputs are 1 A / 5 A, voltage inputs 0–300 V phase-to-neutral, with single and three-pole tripping.

Current inputs
1 A / 5 A
Voltage inputs
0–300 V (ph-n)
Protocols
IEC 61850 Ed.2.1, DNP3, PRP, PTPv2, IEEE C37.118 synchrophasors
Digital substation
optional TiDL or Sampled Values per IEC 61850-9-2 / IEC 61869-9

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The SEL-421 has five zones and controls a two-breaker bay, the SEL-311C has four zones and four-shot autoreclosing, and the new SEL-9L is built on the 9 Series platform and powered from 48–250 V. Logic prevents zone overreach caused by capacitive VTs and covers lines with series compensation. Protocols are IEC 61850 Ed.2.1, DNP3, PRP, PTPv2 and IEEE C37.118 synchrophasors. TiDL or Sampled Values per IEC 61850-9-2 / IEC 61869-9 are optional.

Technical specifications

Current inputs1 A / 5 A
Voltage inputs0–300 V (ph-n)
ProtocolsIEC 61850 Ed.2.1, DNP3, PRP, PTPv2, IEEE C37.118 synchrophasors
Digital substationoptional TiDL or Sampled Values per IEC 61850-9-2 / IEC 61869-9
Zonesup to 5 distance protection zones (mho, quadrilateral)
Trippingsingle- and three-pole
Controltwo-breaker bay
SEL-9L power supply48–250 V

Request a price and lead time

SEL-421 / SEL-311C / SEL-9L — distance protection for power lines. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8536 49 00 90
HS, 6 digits8536 49
CN (EU)8536 49 00
HTSUS (USA)8536 49 00 80
China customs tariff8536 49 00 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

How many distance protection zones do the terminals have?

Up to 5 zones with mho and quadrilateral characteristics. The SEL-421 has five zones and the SEL-311C has four.

Do the terminals support a digital substation?

Yes, TiDL or Sampled Values per IEC 61850-9-2 / IEC 61869-9 are available as options. Communication runs over IEC 61850 Ed.2.1, DNP3, PRP and PTPv2.

What are the analog inputs and the power supply?

Current inputs 1 A / 5 A, voltage inputs 0–300 V phase-to-neutral. The SEL-9L is powered from 48–250 V.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides