Sure-Direct 635EDA220 35 kV elbow arrester for 600 A deadbreak connectors, MCOV 22 kV
The 635EDA220 from the Sure-Direct series is an elbow surge arrester for underground cable networks of 35 kV class, connected to a 600 A deadbreak interface. It has an MCOV of 22 kV, is fully shielded and is suitable for use under water.
- Model
- 635EDA220
- Series
- Sure-Direct
- Type
- elbow arrester for 600 A deadbreak connectors
- Voltage class
- 35 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 635EDA220 arrester from the Sure-Direct series is installed in underground distribution cable networks. It has an elbow shape and connects to a 600 A deadbreak interface that conforms to IEEE Std. 386, interface 13. Typical points of installation are the ends of cable lines at transformers and switchgear, where insulation needs protection against lightning and switching surges.
The housing is fully shielded and insulated, and the product may be used in flooded vaults and manholes. The arrester is interchangeable with products that meet the same requirements. Its design complies with IEEE Std. 386 and IEEE Std. C62.11, section 8.1. The grounding is made with a flexible lead 36 in long.
The class voltage is 35 kV, the duty cycle voltage is 27 kV and the maximum continuous operating voltage (MCOV) is 22 kV. The residual voltage at impulse current is 70.8 kV at 1.5 kA, 75.4 kV at 3 kA, 80.4 kV at 5 kA, 90.5 kV at 10 kA, 104.6 kV at 20 kA and 130.7 kV at 40 kA. The switching surge protective level at 500 A is 69 kV.
The maximum operating altitude is 6000 ft above sea level. The arrester measures 10 in long, 3.65 in wide and 16.5 in high, and its weight is 6.5 lb.
When selecting the arrester, check the MCOV against the highest phase-to-earth voltage of the network and the neutral earthing scheme, and confirm the interface type on the equipment. Compare the residual voltage with the insulation level of the cable and the equipment being protected to obtain the required insulation coordination margin.
Technical specifications
| Model | 635EDA220 |
|---|---|
| Series | Sure-Direct |
| Type | elbow arrester for 600 A deadbreak connectors |
| Voltage class | 35 kV |
| Duty cycle voltage | 27 kV |
| MCOV | 22 kV |
| Residual voltage at 1.5 / 3 / 5 kA | 70.8 / 75.4 / 80.4 kV |
| Residual voltage at 10 / 20 / 40 kA | 90.5 / 104.6 / 130.7 kV |
| Switching surge protective level at 500 A | 69 kV |
| Grounding | flexible lead, 36 in |
| Maximum operating altitude | 6000 ft |
| Dimensions | 10 × 3.65 × 16.5 in |
| Weight | 6.5 lb |
| Standards | IEEE Std. 386 (interface 13), IEEE Std. C62.11 section 8.1 |
Part numbers
Show all part numbers (1)
635EDA220
Request a price and lead time
Sure-Direct 635EDA220 35 kV elbow arrester for 600 A deadbreak connectors, MCOV 22 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which interface does the arrester connect to?
A 600 A deadbreak interface under IEEE Std. 386, interface 13.
What is the residual voltage at 10 kA?
90.5 kV. At 20 kA it is 104.6 kV and at 40 kA it is 130.7 kV.
Can the arrester be installed in flooded vaults?
Yes. It is fully shielded and insulated and suitable for operation under water.