International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

Protecta*Lite line surge arrester 42 kV for 69 kV overhead lines

Protecta*Lite is a line surge arrester for overhead lines above 35 kV, mounted directly on the insulator. Typical versions are rated 42 kV for a 69 kV line, and custom designs are built to order up to 765 kV for distribution and transmission lines.

Type
line surge arrester
Category
EGLA, Line Surge (LSA)
Duty cycle voltage
42 kV
Line voltage
69 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Protecta*Lite line arresters are installed on overhead lines to prevent outages caused by lightning strikes. The arrester attaches to a line insulator in parallel with the string and diverts the overvoltage to the pole, so the insulation does not flash over and the protection does not trip. The manufacturer classes them in the EGLA line surge arrester category.

The arresters work on lines with and without an earth wire. On lines without an earth wire they protect against direct strikes, and on lines with an earth wire they reduce back-flashovers at poles with high earth resistance. Phases and poles for installation are chosen by calculating the lightning performance of the line.

The typical versions 942042G0G0001 and 942042G0G0002 have a duty cycle of 42 kV and are rated for a 69 kV line, with a frequency of 48-62 Hz. They are insulator mounted and meet IEC requirements. The list shows only a selection of typical configurations.

Protecta*Lite assemblies are adapted to the particular distribution or transmission line. The manufacturer builds individual designs up to 765 kV, selecting length, fixings and electrical parameters to suit the pole configuration. These arresters are used where the number of lightning outages must be reduced without rebuilding poles, replacing insulation or adding an earth wire. MCOV is selected from the highest continuous voltage applied between phase and earth in service. An order requires the line voltage class, the insulator and pole type and the earthing scheme.

Technical specifications

Typeline surge arrester
CategoryEGLA, Line Surge (LSA)
Duty cycle voltage42 kV
Line voltage69 kV
Applicationabove 35 kV
Mountingon insulator (insulator mount)
Frequency48-62 Hz
Lineswith and without earth wire
Custom designsup to 765 kV
StandardIEC

Part numbers

Show all part numbers (2)

942042G0G0001, 942042G0G0002

Request a price and lead time

Protecta*Lite line surge arrester 42 kV for 69 kV overhead lines. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can the arrester protect a line without an earth wire?

Yes, Protecta*Lite protects lines both with and without an earth wire. The installation points are chosen by calculating the lightning performance of the line.

Which line voltage is 942042G0G0001 intended for?

A 69 kV line. The arrester duty cycle is 42 kV, with a frequency of 48-62 Hz.

Are arresters made for higher voltages?

Yes, the manufacturer builds individual designs up to 765 kV for distribution and transmission lines.