International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

PVI-LP Station Low surge arrester in polymer housing for systems up to 72.5 kV

PVI-LP are surge arresters with a solid active core for medium-voltage substations, classed as Station Low under IEC 60099-4 and Intermediate under IEEE C62.11. They are intended for systems up to 72.5 kV and have a compact housing for confined switchgear.

Type
station surge arrester, polymer housing
Class
Station Low (IEC), Intermediate (IEEE)
System voltage
up to 72.5 kV
MCOV / Uc
2.55 to 57 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

PVI-LP arresters are installed in substations to protect transformers, switching devices and other equipment from lightning and switching overvoltages. They divert excess voltage to earth and are rated for systems up to 72.5 kV. The compact design suits switchgear where space is limited.

The active part is a solid core built from MOV varistor discs. The housing is moulded from grey ESP polymer with high mechanical strength. A sealing system keeps moisture away from the internal elements and extends service life. The maximum cantilever bending strength is 4000 in lbs, and the pressure relief capability is 40 kA symmetrical rms.

The series covers MCOV values from 2.55 to 57 kV: 2.55, 5.1, 7.65, 8.4, 10.2, 12.7, 15.3, 17, 19.5, 22, 24.4, 29, 31.5, 36, 39, 42, 48 and 57 kV. Model 3006103001 with an MCOV of 10.2 kV has a duty cycle of 12 kV, a height of 6.8 in and a base width of 11.5 in. Height rises with MCOV: 12.2 in for 19.5 kV, 17.6 in for 29 kV, 28.4 in for 48 kV and 33.8 in for 57 kV, the last with a 72 kV duty cycle.

For 3006103001 the residual voltage is 28.1 kV at 1.5 kA, 32.3 kV at 10 kA and 40.3 kV at 40 kA. The creepage distance is 4.9 in (124.46 mm), the frequency range is 48-62 Hz and the altitude is up to 12000 ft. The arrester is mounted on a small top base or tripod, the connection is made through single eyebolt terminals, and the base bolt circle is 8.75 in in diameter. Minimum phase-to-phase spacing at sea level is 15.4 in (391 mm), and minimum spacing to earthed parts is 3.5 in (88.9 mm). The design complies with IEEE C62.11 and IEC 60099-4, 2004-05 Edition 3.0.

Technical specifications

Typestation surge arrester, polymer housing
ClassStation Low (IEC), Intermediate (IEEE)
System voltageup to 72.5 kV
MCOV / Uc2.55 to 57 kV
Duty cycle voltage12 kV (3006103001) … 72 kV (3008573010)
Residual voltage 300610300128.1 kV at 1.5 kA; 40.3 kV at 40 kA
Pressure relief40 kA symmetrical rms
Maximum cantilever bending strength4000 in lbs
Housing materialESP polymer, grey
Creepage distance4.9 in (124.46 mm)
Height6.8 to 33.8 in
Base width / depth11.5 in
Base bolt circle diameter8.75 in
Minimum phase-to-phase spacing15.4 in (391 mm)
Frequency48-62 Hz
Altitudeup to 12000 ft
StandardsIEEE C62.11, IEC 60099-4

Part numbers

Show all part numbers (32)

3006103001, 3006203001, 3006203012, 3006293001, 3006293012, 3006393001, 3006423001, 3006483001, 3006483022, 3006573001, 3008033001, 3008053001, 3008053012, 3008083001, 3008083002, 3008093001, 3008093012, 3008133001, 3008153001, 3008173001, 3008173012, 3008203010, 3008223001, 3008243001, 3008243012, 3008293010, 3008313001, 3008363010, 3008423010, 3008483001, 3008483010, 3008573010

Request a price and lead time

PVI-LP Station Low surge arrester in polymer housing for systems up to 72.5 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which system voltage does the PVI-LP suit?

Systems up to 72.5 kV, with MCOV values from 2.55 to 57 kV in the series. For example, 3008573010 has an MCOV of 57 kV and a duty cycle of 72 kV.

Which standards does the arrester meet?

IEC 60099-4 for the Station Low class and IEEE C62.11 for the Intermediate class.

How is the arrester mounted?

On a small top base or tripod with single eyebolt terminals. The base bolt circle diameter is 8.75 in and the minimum phase-to-phase spacing is 15.4 in (391 mm).