Sure-Break Elbow 200 A 28 kV elbow arrester for separable connectors
Sure-Break Elbow arresters connect to the bushings of transformers and cabinets in underground networks rated 200 A. The increased flashover distance improves switching conditions during partial vacuum flashover, and the design meets IEEE Std. 386 and IEEE Std. C62.11 section 8.1.
- Type
- elbow arrester
- Series
- Sure-Break Elbow
- Connector rating
- 200 A
- Voltage class
- 25 kV (marked 28 kV)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
An elbow arrester is fitted to the bushing of a transformer or switchgear at a site, a sectionalising cabinet or a switching device of an underground cable network. It has the form of an elbow-shaped separable connector and protects equipment against lightning and switching overvoltages at the point where the cable connects.
The housing is polymer, fully shielded and insulated, and can be submerged. The earthing uses a 36 inch line lead. The Sure-Break series has an increased flashover distance, which improves switching conditions during partial vacuum flashover. The product is interchangeable with other products that meet the same IEEE Std. 386 requirements.
The 200 A models marked 28 kV have a 25 kV voltage class. 228ELAS06 has an MCOV of 5.1 kV and a duty cycle of 6 kV, with a maximum switching surge of 17.0 kV. 228ELAS09 has an MCOV of 7.65 kV, a duty cycle of 9 kV and a switching surge of 23.0 kV. 228ELAS12 has an MCOV of 10.2 kV, a duty cycle of 12 kV and a switching surge of 34.0 kV. The one-minute AC withstand voltage is 25 kV.
Residual voltage for 228ELAS09 is 23.6 kV at 1.5 kA, 30.2 kV at 10 kA and 43.6 kV at 40 kA. For 228ELAS12 the same current points give 31.5 kV, 40.2 kV and 58.1 kV. Each model weighs 3.7 lb, measures 3.0625 inch wide and 7.75 inch long, and has a height of 10.185, 11.25 or 11.625 inch depending on MCOV. The 35 kV class includes 235ELA27, with an MCOV of 22 kV for a small 7B interface, and 635EDA270 from the Sure-Direct series, rated 600 A with an MCOV of 27 kV for deadbreak connections with a 13 interface. The maximum installation altitude is 6000 ft, and MCOV is selected from the highest continuous phase-to-earth voltage of the network.
Technical specifications
| Type | elbow arrester |
|---|---|
| Series | Sure-Break Elbow |
| Connector rating | 200 A |
| Voltage class | 25 kV (marked 28 kV) |
| MCOV | 5.1; 7.65; 10.2 kV |
| Duty cycle voltage | 6; 9; 12 kV |
| Maximum switching surge | 17.0; 23.0; 34.0 kV |
| One-minute AC withstand | 25 kV |
| Residual voltage 228ELAS12 | 31.5 kV at 1.5 kA; 58.1 kV at 40 kA |
| Material | polymer |
| Earthing | 36 in lead |
| Dimensions | 7.75 x 3.0625 x 10.185 to 11.625 in |
| Weight | 3.7 lb |
| Installation altitude | up to 6000 ft |
| Standards | IEEE Std. 386, IEEE Std. C62.11 section 8.1 |
Part numbers
Show all part numbers (5)
228ELAS06, 228ELAS09, 228ELAS12, 235ELA27, 635EDA270
Request a price and lead time
Sure-Break Elbow 200 A 28 kV elbow arrester for separable connectors. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How does the Sure-Break series differ from a standard elbow arrester?
It has an increased flashover distance, which improves switching conditions during partial vacuum flashover. Its connection dimensions meet IEEE Std. 386.
Which MCOV should be chosen for a 25 kV class network?
5.1, 7.65 and 10.2 kV are available, chosen by the highest continuous phase-to-earth voltage. For the 35 kV class there is 235ELA27 with an MCOV of 22 kV.
Is a 600 A version available?
Yes, 635EDA270 from the Sure-Direct series is rated 600 A and 35 kV class with an MCOV of 27 kV, for deadbreak connections with a 13 interface.
Similar equipment from other manufacturers