Elbow Surge Arresters 215ELA, 225ELA, 236ELA and 635EDA for 15–35 kV, 200 A and 600 A
Elbow arresters protect underground distribution networks of the 15, 25, 28 and 35 kV classes. They connect straight onto a transformer or distribution point terminal in place of a cable elbow, with MCOV ratings from 2.55 kV to 29 kV across 200 A and 600 A interfaces.
- Type
- Elbow Arrester, Underground Arresters
- Voltage classes
- 15 kV, 25 kV, 28 kV, 35 kV
- MCOV range
- 2.55 kV to 29 kV
- Interface current rating
- 200A, 600A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Elbow arresters guard underground distribution networks against lightning and switching surges. The unit has a separable connector interface and fits directly to the entry of a transformer, a switch or a feed-through bushing, so it protects the exact point that needs protection. Several duty-cycle ratings are offered, so within one voltage class you can choose a unit suited to the neutral earthing of the network.
The polymer housing is fully shielded and insulated, and the unit can be submerged. The arresters are built to IEEE Std. 386 and IEEE Std. C62.11, Section 8.1, and are interchangeable with other products that meet the same requirements. Earthing uses a 36 in line lead, and the maximum operating altitude is 6000 ft.
The 15 kV class (215ELA) spans MCOV values of 2.55, 5.1, 7.65, 8.4, 10.2, 12.7 and 15.3 kV. The 215ELA06 has an MCOV of 5.1 kV, a duty cycle of 6 kV and a maximum switching surge of 17.0 kV, with residual voltage from 19.5 kV at 1.5 kA up to 37 kV at 40 kA. The 215ELA09 has an MCOV of 7.65 kV, a duty cycle of 9 kV and a switching surge of 23.0 kV, with residual voltage from 26.8 kV at 1.5 kA up to 50.5 kV at 40 kA. Units in this class measure 8.438 in by 2.85 in by 9.438 in, and the 215ELA06 and 215ELA09 weigh 3.700 lb.
The 25 kV class (225ELA) covers MCOV values from 7.65 to 17 kV. The 28 kV elbow series (228ELAS) is offered with MCOV values of 2.55, 8.4, 15.3 and 17 kV. For the 35 kV class there is a small-interface type, 235ELA, with MCOV values of 19.5 and 24.4 kV, and a large-interface type, 236ELA, with MCOV values of 22, 24.4, 27 and 29 kV. All of these units have a 200 A interface.
For 35 kV units with 600 A interfaces, the 635EDA220, 635EDA244 and 635EDA290 have MCOV values of 22, 24.4 and 29 kV. A separate shielded back arrester, WHCCK9175, of type YH5WZ-17/45 is rated 17 kV, and the manufacturer states that it conforms to IEC60099-4 and GB/T11032-2020. To select a unit, state the voltage class of the network, the neutral earthing method, the interface type (small or large, 200 A or 600 A) and the MCOV required.
Technical specifications
| Type | Elbow Arrester, Underground Arresters |
|---|---|
| Voltage classes | 15 kV, 25 kV, 28 kV, 35 kV |
| MCOV range | 2.55 kV to 29 kV |
| Interface current rating | 200A, 600A |
| Interfaces | IEEE Std. 386 (Interfaces 7B, 9, 13) |
| MCOV 215ELA | 2.55; 5.1; 7.65; 8.4; 10.2; 12.7; 15.3 kV |
| MCOV 225ELA | 7.65; 8.4; 10.2; 12.7; 15.3; 17 kV |
| MCOV 236ELA (35 kV, large interface) | 22; 24.4; 27; 29 kV |
| MCOV 635EDA (35 kV, 600A) | 22; 24.4; 29 kV |
| 215ELA06 | MCOV 5.1 kV, duty cycle 6 kV, switching surge 17.0 kV |
| 215ELA09 | MCOV 7.65 kV, duty cycle 9 kV, switching surge 23.0 kV |
| Material | Polymer |
| Earthing | 36 in line lead |
| Maximum operating altitude | 6000 ft |
| Dimensions 215ELA | 8.438 in x 2.85 in x 9.438 in |
| Weight 215ELA06, 215ELA09 | 3.700 lb. |
| Standards | IEEE Std. 386, IEEE Std. C62.11 Section 8.1, IEC60099-4, GB/T11032-2020 |
Part numbers
Show all part numbers (27)
215ELA03, 215ELA06, 215ELA09, 215ELA10, 215ELA12, 215ELA15, 215ELA18, 225ELA09, 225ELA10, 225ELA12, 225ELA15, 225ELA18, 225ELA21, 228ELAS03, 228ELAS10, 228ELAS18, 228ELAS21, 235ELA24, 235ELA30, 236ELA27, 236ELA30, 236ELA33, 236ELA36, 635EDA220, 635EDA244, 635EDA290, WHCCK9175
Request a price and lead time
Elbow Surge Arresters 215ELA, 225ELA, 236ELA and 635EDA for 15–35 kV, 200 A and 600 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the 235ELA and 236ELA series differ?
Both series are rated for the 35 kV class with a 200 A interface. The 235ELA uses a small interface with MCOV values of 19.5 and 24.4 kV, whereas the 236ELA uses a large interface with MCOV values from 22 to 29 kV.
Are there elbow arresters with 600 A interfaces?
Yes. The 635EDA220, 635EDA244 and 635EDA290 are 35 kV, 600 A units with MCOV values of 22, 24.4 and 29 kV.
What is the residual voltage of the 215ELA09?
It is 26.8 kV at 1.5 kA, 33 kV at 10 kA and 50.5 kV at 40 kA. Its MCOV is 7.65 kV and its duty cycle is 9 kV.
Similar equipment from other manufacturers