Polymer-Housed Substation Surge Arresters PVI-LP, EVP and SVN to IEEE C62.11
A family of metal-oxide arresters in polymer housings for substation duty on systems from 2.5 kV to 800 kV. It spans the intermediate-class PVI-LP and the station-class EVP, SVN, SVNH and SVNX lines, all built to IEEE C62.11.
- Series
- PVI-LP, EVP, SVN, SVNH, SVNX
- Family system voltage
- 2.5–800 kV
- Standards
- IEEE C62.11, IEC 60099-4
- PVI-LP IEEE class
- intermediate
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Take the 29 kV MCOV PVI-LP, catalogue number 3006293010, as a reference point. It discharges 84.4 kV at 1.5 kA, 88.6 kV at 3 kA, 92.8 kV at 5 kA, 96.9 kV at 10 kA and 108.8 kV at 20 kA, with 111.3 kV on a 0.5 microsecond front. Switching surge protective level at 500 A is 78.4 kV, pressure relief is rated at 40 kA symmetrical rms and the low current long duration test lasts 2000 microseconds.
Physically that unit stands 17.6 in high and measures 11.5 in across both width and depth, for 48–62 Hz networks. Other PVI-LP ratings, such as 36.5 kV MCOV on 3006363001 with single eyebolt terminals, take a maximum cantilever of 4,000 in lbs.
The PVI-LP is a solid-core design: a stack of MOV discs with no internal air space, enclosed in grey ESP polymer that combines good mechanical strength with stable electrical behaviour. A sealing system keeps moisture away from the internals over a long service life. The series is tested against the latest revisions of both IEEE C62.11 and IEC 60099-4, so it can be specified on IEC and IEEE networks alike.
Choosing between lines comes down to the IEEE class needed at the bay. PVI-LP covers intermediate duty, whereas EVP, SVN, SVNH and SVNX are station-class units for transformer and switchgear protection on larger installations. Send us the system voltage, MCOV and terminal arrangement and we will match the catalogue number.
Technical specifications
| Series | PVI-LP, EVP, SVN, SVNH, SVNX |
|---|---|
| Family system voltage | 2.5–800 kV |
| Standards | IEEE C62.11, IEC 60099-4 |
| PVI-LP IEEE class | intermediate |
| Construction | solid core, MOV discs |
| PVI-LP housing | ESP polymer, grey |
| Frequency | 48–62 Hz |
| MCOV (example 3006293010) | 29 kV |
| Pressure relief | 40 kA |
| LCLD test duration | 2000 µs |
| Discharge voltage at 10 kA | 96.9 kV |
| Height × width × depth | 17.6 × 11.5 × 11.5 in |
| Max cantilever (3006363001) | 4,000 in lbs |
Request a price and lead time
Polymer-Housed Substation Surge Arresters PVI-LP, EVP and SVN to IEEE C62.11. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What separates PVI-LP from the SVN line?
PVI-LP is an IEEE intermediate-class arrester, while SVN, SVNH, SVNX and EVP are station class; all use polymer housings and meet IEEE C62.11.
What discharge voltage does the 29 kV MCOV PVI-LP give at 10 kA?
96.9 kV, rising to 108.8 kV at 20 kA and falling to 84.4 kV at 1.5 kA.
Can these units go on an IEC network?
Yes, the PVI-LP also complies with IEC 60099-4 and is rated for 48–62 Hz.