International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

PDV-65 Optima Normal Duty Distribution Arresters for 2.5–36 kV Networks

Polymer-housed metal-oxide arresters for overhead distribution lines from 2.5 kV to 36 kV, built to IEEE C62.11. They guard pole-mounted transformers, switchgear and similar plant on residential and light industrial feeders against moderate surges, mostly from lightning.

Series
PDV-65 Optima
Class
Normal Duty (IEEE); Distribution Medium (IEC)
System voltage
2.5–36 kV
Standard
IEEE C62.11

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Every PDV-65 Optima is identified by its MCOV and a hardware code at the end of the catalogue number, such as 7202 or 7114, so one rating can be ordered with different fixings for the pole. Under IEEE the series is Normal Duty, and under IEC it corresponds to Distribution Medium.

Versions fitted with the capacitive disconnector separate from the line at fault currents as low as 1 A, so a failed unit hangs visibly detached from the line. Internally the MOV discs sit in a grey ESP polymer housing with good mechanical strength, and a dynamic triple seal keeps moisture out. Each unit is routine tested.

As a worked example, 2132637202 is a 12.7 kV MCOV unit with a 15 kV duty cycle rating, supplied without disconnector or bracket for upright mounting. It handles 48–62 Hz, has 15 kA pressure relief and is tested for low current long duration at 75 A over 2000 microseconds. Leakage distance is 592 mm (23.3 in) and minimum strike 9.7 in.

Its discharge voltages are 39.9 kV at 1.5 kA, 45.3 kV at 5 kA, 51 kV at 10 kA, 58.9 kV at 20 kA and 73.7 kV at 40 kA, with 50.6 kV on a 0.5 microsecond front and a switching surge protective level of 35.7 kV at 500 A. The body measures 11.13 by 3.63 by 3.63 in, fixes on a 3/8-16 stud and accepts a cantilever moment of 45 Nm.

Technical specifications

SeriesPDV-65 Optima
ClassNormal Duty (IEEE); Distribution Medium (IEC)
System voltage2.5–36 kV
StandardIEEE C62.11
HousingESP polymer, grey
Frequency48–62 Hz
Disconnectorcapacitive, from 1 A (version dependent)
MCOV / duty cycle (2132637202)12.7 kV / 15 kV
Pressure relief15 kA
LCLD75 A, 2000 µs
Discharge voltage at 10 kA (2132637202)51 kV
Leakage distance (2132637202)592 mm
Stud3/8-16
Cantilever moment45 Nm

How it compares with similar models

ParameterPDV-65 Optima Normal Duty Distribution Arresters for 2.5–36 kV NetworksPDV-100 Optima heavy-duty polymer surge arrester to IEEE C62.11, 2.5–36 kV networksEVP Polymer Station Arresters, IEC Station Medium and IEEE Station ClassPolymer-housed distribution surge arresters to IEEE C62.11, normal and heavy duty
ClassNormal Duty (IEEE); Distribution Medium (IEC)IEEE heavy duty, distributionstation (IEEE); Station Medium (IEC)—
HousingESP polymer, greyESP™ polymer, greyESP polymer, greypolymer
Pressure relief15 kA20 kA sym. rms63 kA—

Request a price and lead time

PDV-65 Optima Normal Duty Distribution Arresters for 2.5–36 kV Networks. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What network voltages does the series cover?

Distribution systems from 2.5 kV to 36 kV; the 12.7 kV MCOV unit carries a 15 kV duty cycle rating.

How does the disconnector behave?

On versions that have it, the capacitive disconnector operates at fault currents down to 1 A; 2132637202 is supplied without one.

How do I specify the mounting hardware?

Quote the hardware code at the end of the catalogue number, for example 7202 or 7114, or tell us the pole arrangement and we will match it.