PDV-100 Optima heavy-duty polymer surge arrester to IEEE C62.11, 2.5–36 kV networks
A metal-oxide surge arrester in a grey ESP™ polymer housing for 2.5–36 kV distribution networks, tested to the heavy-duty class of IEEE C62.11. It suits lines exposed to frequent high-energy lightning and switching surges, such as industrial feeders.
- Class
- IEEE heavy duty, distribution
- Standard
- IEEE C62.11
- System voltage
- 2.5–36 kV
- MCOV (part 2137037202)
- 2.55 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Inside the grey ESP™ polymer housing sits a stack of metal-oxide varistor discs, kept dry by a triple dynamic sealing arrangement. Every unit is routine tested before dispatch. On versions fitted with a disconnector, the capacitive disconnector operates at fault currents as low as 1 A, so a failed arrester drops clear of the line instead of leaving a permanent fault.
Take catalogue number 2137037202 as the reference: MCOV 2.55 kV, no disconnector. Its residual voltage is 8 kV at 1.5 kA, 9.9 kV at 10 kA and 13.3 kV at 40 kA, while the switching surge level stays at 7.3 kV. Pressure relief is rated at 20 kA symmetrical rms, and the low-current long-duration test runs at 250 A for 2000 µs. Creepage distance is 215 mm (8.5 in).
The heavy-duty rating matters on rural overhead feeders, transformer taps and plant substations where strikes are frequent and surge energy is high. Utilities and industrial sites use these arresters to keep transformers, cable terminations and switchgear inside their insulation margins.
The range covers dozens of part numbers, split by MCOV rating and by the bracket and hardware set supplied. Units are mounted upright on a 3/8-16 stud, with a maximum cantilever moment of 80 Nm, and operate at 48–62 Hz. The reference unit weighs 1.7 lb and measures 9.313 × 4.1 × 6.13 in. Send us your system voltage and earthing arrangement and we will match the MCOV and hardware.
Technical specifications
| Class | IEEE heavy duty, distribution |
|---|---|
| Standard | IEEE C62.11 |
| System voltage | 2.5–36 kV |
| MCOV (part 2137037202) | 2.55 kV |
| Duty cycle | 3 kV |
| Residual voltage | 8 kV @ 1.5 kA; 9.9 kV @ 10 kA; 13.3 kV @ 40 kA |
| Switching surge, max. | 7.3 kV |
| Pressure relief | 20 kA sym. rms |
| LCLD test | 250 A, 2000 µs |
| Creepage distance | 215 mm (8.5 in) |
| Frequency | 48–62 Hz |
| Housing | ESP™ polymer, grey |
| Cantilever moment, max. | 80 Nm |
| Dimensions | 9.313 × 4.1 × 6.13 in |
| Stud | 3/8-16 |
How it compares with similar models
| Parameter | PDV-100 Optima heavy-duty polymer surge arrester to IEEE C62.11, 2.5–36 kV networks | PDV-100 Optima IEC Distribution High arrester, M12 stud, for 2.5–36 kV networks | PDV-65 Optima normal-duty distribution arrester, IEC 60099-4 Ed. 3.0 class DM, 2.5–36 kV | PDV-65 Optima Normal Duty Distribution Arresters for 2.5–36 kV Networks |
|---|---|---|---|---|
| Class | IEEE heavy duty, distribution | IEC Distribution High / IEEE heavy duty | IEC Distribution Medium / IEEE normal duty | Normal Duty (IEEE); Distribution Medium (IEC) |
| Standard | IEEE C62.11 | IEC 60099-4 Edition 3.0 | IEC 60099-4 Edition 3.0 | IEEE C62.11 |
| Residual voltage | 8 kV @ 1.5 kA; 9.9 kV @ 10 kA; 13.3 kV @ 40 kA | 8 kV @ 1.5 kA; 9.9 kV @ 10 kA; 13.3 kV @ 40 kA | 8.1 kV @ 1.5 kA; 10.4 kV @ 10 kA; 15 kV @ 40 kA | — |
| Pressure relief | 20 kA sym. rms | 20 kA sym. rms | 16 kA sym. rms | 15 kA |
| LCLD test | 250 A, 2000 µs | 250 A, 2000 µs | 75 A, 2000 µs | — |
| Creepage distance | 215 mm (8.5 in) | 215 mm (8.5 in) | 338 mm (13.3 in) | — |
Request a price and lead time
PDV-100 Optima heavy-duty polymer surge arrester to IEEE C62.11, 2.5–36 kV networks. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which system voltages does the PDV-100 Optima range cover?
Distribution systems from 2.5 kV up to 36 kV, with the unit chosen by MCOV, starting at 2.55 kV.
Can I order it with a disconnector?
Yes, several part numbers carry a capacitive disconnector that operates from 1 A of fault current; part 2137037202 is supplied without one.
What test standard applies?
The range is tested to IEEE C62.11 for heavy-duty distribution arresters.