International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

PDV-100 Optima heavy-duty polymer surge arrester to IEEE C62.11, 2.5–36 kV networks

A metal-oxide surge arrester in a grey ESP™ polymer housing for 2.5–36 kV distribution networks, tested to the heavy-duty class of IEEE C62.11. It suits lines exposed to frequent high-energy lightning and switching surges, such as industrial feeders.

Class
IEEE heavy duty, distribution
Standard
IEEE C62.11
System voltage
2.5–36 kV
MCOV (part 2137037202)
2.55 kV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Inside the grey ESP™ polymer housing sits a stack of metal-oxide varistor discs, kept dry by a triple dynamic sealing arrangement. Every unit is routine tested before dispatch. On versions fitted with a disconnector, the capacitive disconnector operates at fault currents as low as 1 A, so a failed arrester drops clear of the line instead of leaving a permanent fault.

Take catalogue number 2137037202 as the reference: MCOV 2.55 kV, no disconnector. Its residual voltage is 8 kV at 1.5 kA, 9.9 kV at 10 kA and 13.3 kV at 40 kA, while the switching surge level stays at 7.3 kV. Pressure relief is rated at 20 kA symmetrical rms, and the low-current long-duration test runs at 250 A for 2000 µs. Creepage distance is 215 mm (8.5 in).

The heavy-duty rating matters on rural overhead feeders, transformer taps and plant substations where strikes are frequent and surge energy is high. Utilities and industrial sites use these arresters to keep transformers, cable terminations and switchgear inside their insulation margins.

The range covers dozens of part numbers, split by MCOV rating and by the bracket and hardware set supplied. Units are mounted upright on a 3/8-16 stud, with a maximum cantilever moment of 80 Nm, and operate at 48–62 Hz. The reference unit weighs 1.7 lb and measures 9.313 × 4.1 × 6.13 in. Send us your system voltage and earthing arrangement and we will match the MCOV and hardware.

Technical specifications

ClassIEEE heavy duty, distribution
StandardIEEE C62.11
System voltage2.5–36 kV
MCOV (part 2137037202)2.55 kV
Duty cycle3 kV
Residual voltage8 kV @ 1.5 kA; 9.9 kV @ 10 kA; 13.3 kV @ 40 kA
Switching surge, max.7.3 kV
Pressure relief20 kA sym. rms
LCLD test250 A, 2000 µs
Creepage distance215 mm (8.5 in)
Frequency48–62 Hz
HousingESP™ polymer, grey
Cantilever moment, max.80 Nm
Dimensions9.313 × 4.1 × 6.13 in
Stud3/8-16

How it compares with similar models

ParameterPDV-100 Optima heavy-duty polymer surge arrester to IEEE C62.11, 2.5–36 kV networksPDV-100 Optima IEC Distribution High arrester, M12 stud, for 2.5–36 kV networksPDV-65 Optima normal-duty distribution arrester, IEC 60099-4 Ed. 3.0 class DM, 2.5–36 kVPDV-65 Optima Normal Duty Distribution Arresters for 2.5–36 kV Networks
ClassIEEE heavy duty, distributionIEC Distribution High / IEEE heavy dutyIEC Distribution Medium / IEEE normal dutyNormal Duty (IEEE); Distribution Medium (IEC)
StandardIEEE C62.11IEC 60099-4 Edition 3.0IEC 60099-4 Edition 3.0IEEE C62.11
Residual voltage8 kV @ 1.5 kA; 9.9 kV @ 10 kA; 13.3 kV @ 40 kA8 kV @ 1.5 kA; 9.9 kV @ 10 kA; 13.3 kV @ 40 kA8.1 kV @ 1.5 kA; 10.4 kV @ 10 kA; 15 kV @ 40 kA—
Pressure relief20 kA sym. rms20 kA sym. rms16 kA sym. rms15 kA
LCLD test250 A, 2000 µs250 A, 2000 µs75 A, 2000 µs—
Creepage distance215 mm (8.5 in)215 mm (8.5 in)338 mm (13.3 in)—

Request a price and lead time

PDV-100 Optima heavy-duty polymer surge arrester to IEEE C62.11, 2.5–36 kV networks. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which system voltages does the PDV-100 Optima range cover?

Distribution systems from 2.5 kV up to 36 kV, with the unit chosen by MCOV, starting at 2.55 kV.

Can I order it with a disconnector?

Yes, several part numbers carry a capacitive disconnector that operates from 1 A of fault current; part 2137037202 is supplied without one.

What test standard applies?

The range is tested to IEEE C62.11 for heavy-duty distribution arresters.