MH4 and PH4 Station High Surge Arresters to IEC 60099-4, 36–420 kV Systems
High-voltage substation arresters in the IEC 60099-4 Station High class, covering system voltages from 36 kV to 420 kV. The MH4 line uses a hollow-core porcelain housing and holds IEEE 693 High Performance qualification for seismic sites.
- Series
- MH4, PH4
- IEC 60099-4 class
- Station High
- System voltage
- 36–420 kV
- MH4 housing
- porcelain, hollow core, grey or brown
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Consider MH4036GM030AA, built for a 36 kV system with Ur 30 kV and Uc 24 kV. Its leakage distance is 1116 mm (43.9 in), and the housing withstands 276 kV lightning impulse, 220 kV switching impulse and 108 kV wet at 60 Hz. Residual voltage reads 62.5 kV at 1.5 kA, 70.5 kV at 10 kA and 83.5 kV at 40 kA, while switching protective levels are 59.0 kV at 500 A, 60.5 kV at 1000 A and 62.5 kV at 2000 A.
Installation details are common across the range. Units mount upright on a 254 mm bolt circle with 14 mm holes and suit 48–62 Hz networks. Pressure relief is rated at 63 kA symmetrical rms. On the 36 kV example the line terminal takes Cu or Al conductors from AWG #4 to 500 MCM, minimum strike distance is 445.0 mm, and the sea-level spacing should be at least 131 mm to earth and 165 mm phase to phase. Height is 31.7 in and width and depth 12 in each.
The MH4 housing is porcelain, grey or brown, around a hollow core, and the line has passed IEEE 693 High Performance qualification, which matters for substations in seismic zones. Every unit is routine tested before it leaves the works.
Within one rating several creepage options exist; a 48 kV MH4 comes with either 1116 mm or 1905 mm of leakage distance, so heavily polluted sites can be served without moving up a voltage class. PH4 completes the family for the same 36–420 kV band. Give us the system voltage, Ur and pollution level and we will select the catalogue number.
Technical specifications
| Series | MH4, PH4 |
|---|---|
| IEC 60099-4 class | Station High |
| System voltage | 36–420 kV |
| MH4 housing | porcelain, hollow core, grey or brown |
| Seismic qualification | IEEE 693 High Performance |
| Frequency | 48–62 Hz |
| Pressure relief | 63 kA |
| Base bolt circle | 254 mm |
| Mounting holes | 14 mm |
| Ur / Uc (MH4036GM030AA) | 30 kV / 24 kV |
| Leakage distance (MH4036GM030AA) | 1116 mm |
| Lightning impulse withstand (MH4036GM030AA) | 276 kV |
| Residual voltage at 10 kA (MH4036GM030AA) | 70.5 kV |
| Conductors | Cu/Al, AWG #4–500 MCM |
How it compares with similar models
| Parameter | MH4 and PH4 Station High Surge Arresters to IEC 60099-4, 36–420 kV Systems | EVP Polymer Station Arresters, IEC Station Medium and IEEE Station Class | PDV-65 Optima Normal Duty Distribution Arresters for 2.5–36 kV Networks | IEC 60099-4 distribution surge arresters for 2.5–36 kV networks |
|---|---|---|---|---|
| System voltage | 36–420 kV | — | 2.5–36 kV | 2.5–36 kV |
| Pressure relief | 63 kA | 63 kA | 15 kA | — |
Request a price and lead time
MH4 and PH4 Station High Surge Arresters to IEC 60099-4, 36–420 kV Systems. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Is MH4 suitable for a seismic zone?
Yes, the porcelain MH4 carries IEEE 693 High Performance qualification.
Can I get extra creepage without a higher rating?
Yes, for example a 48 kV MH4 is offered with 1116 mm or 1905 mm leakage distance.
What base does the arrester need?
An upright mounting on a 254 mm bolt circle with 14 mm holes.