UGFI / ARU / CR / TPR and RadioRANGER — fault indicators for cable networks
LINAM UGFI, ARU, CR and TPR indicate the damaged section of an underground MV cable network. Trip threshold 25–1600 A, withstand of up to 40 kA for 10 cycles, submersible design.
- Trip threshold
- 25–1600 A
- Short-circuit current
- up to 40 kA, 10 cycles
- Cable joints
- 15, 25, 35 kV (TPR)
- Design
- submersible
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The fault indicators are protected against the influence of adjacent phases, and the threshold is selected automatically by the AutoRANGER function. Resetting is done by current or by voltage. TPR models are installed on 15, 25 and 35 kV cable joints. RadioRANGER allows reading indicator status in manholes by radio from the surface, without sending personnel down. The submersible design suits flooded manholes, per IEEE 495.
Technical specifications
| Trip threshold | 25–1600 A |
|---|---|
| Short-circuit current | up to 40 kA, 10 cycles |
| Cable joints | 15, 25, 35 kV (TPR) |
| Design | submersible |
| Standard | IEEE 495 |
Request a price and lead time
UGFI / ARU / CR / TPR and RadioRANGER — fault indicators for cable networks. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 9030 33 70 00 |
|---|---|
| HS, 6 digits | 9030 33 |
| CN (EU) | 9030 33 70 |
| HTSUS (USA) | 9030 33 38 00 |
| China customs tariff | 9030 33 90 00 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
What is the threshold range of the indicators?
The trip threshold is 25–1600 A, and in AutoRANGER mode it is selected automatically.
What fault current does the indicator withstand?
Up to 40 kA for 10 cycles, tested to IEEE 495.
Which joints are the TPR indicators installed on?
TPR models are made for 15, 25 and 35 kV cable joints.
Similar equipment from other manufacturers