TWS FL-8 and TWS FL-1 Travelling Wave Fault Locators for Up to 8 Lines

The TWS FL-8 and TWS FL-1 locate faults on overhead lines and cables using the travelling wave method, to within one tower span. Installation needs no line or substation outage, and fault results reach the dispatch centre within minutes of the breaker tripping.

Models
TWS FL-8 (2–8 lines), TWS FL-1 (1 line)
Method
Travelling wave, accuracy to one tower span
Channels
3 per line (one per phase), 12-bit ADC
Sampling rate
20 MHz, 10 MHz, 5 MHz, 2.5 MHz or 1.25 MHz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The FL-8 is modular, with two line boards at base that expand in steps of two up to eight lines. It sits in a 3U case measuring 132.5 × 487 × 362.2 mm and weighing 11 kg. The FL-1 uses a fixed format with a single line board in a 2U case that is 90 mm high. Each line takes three channels, one per phase, from external line sensors, digitised by a 12-bit converter at sampling rates from 1.25 to 20 MHz.

Time is synchronised either by the built-in GPS module in master mode, or over the local network through NTP with a 1 pps signal in slave mode. Accuracy is 100 ns for the master and 1 microsecond for the slave. An IRIG-B output can synchronise other intelligent devices in the substation, and measurements are unaffected by phase transpositions or mutual coupling between lines.

Records are kept on a 4 GB CompactFlash card, which holds 2100 records from eight line boards at 2.5 MHz, and an 8 GB card is available on request. Communication uses two 100 Mbit Ethernet ports, one at the front and one at the rear with an optical option, alongside three RS 232 ports, one RS 485 port and a USB port for firmware updates and data retrieval. An optional PSTN modem is also available, and staff receive alerts by email.

The method works on overhead lines and underground cables, and it detects permanent, intermittent and self-clearing faults. Tracking intermittent faults lets crews target a specific point on the line before the defect leads to a serious failure. The units replace the earlier TWS Mark VI and DSFL models, and the data can be integrated with fault recorders and mapping software.

The unit mounts in a 19-inch rack with IP 41 protection. It runs on 88 to 300 VDC or VAC, with a 36 to 72 VDC option, draws 20 VA and provides a 12 VDC 750 mA auxiliary output. The operating range is -5 to +50 °C with humidity from 0 to 95 % non-condensing. The GPS antenna on a 10 m cable is fixed to a mast made from 25 mm pipe.

Technical specifications

ModelsTWS FL-8 (2–8 lines), TWS FL-1 (1 line)
MethodTravelling wave, accuracy to one tower span
Channels3 per line (one per phase), 12-bit ADC
Sampling rate20 MHz, 10 MHz, 5 MHz, 2.5 MHz or 1.25 MHz
MemoryCompactFlash 4 GB, 2100 records (8 lines, 2.5 MHz); 8 GB option
SynchronisationGPS (master) or NTP + 1 pps (slave)
Synchronisation accuracy100 ns (master), 1 microsecond (slave)
Sync outputIRIG-B
Interfaces2 × Ethernet 100 Mbit RJ45 (optical option), 3 × RS 232, 1 × RS 485, USB
Alarms4 relays: 1 NC (healthy), 3 NO
DisplayBacklit LCD 114 × 49 mm, 240 × 80 dots, 7-button keypad
Power supply88–300 VDC/VAC, 42.5–67.5 Hz (36–72 VDC option), 20 VA
Operating temperature-5…+50 °C
Storage temperature-30…+70 °C
Humidity0–95% non-condensing
EnclosureIP 41, 19-inch rack
TWS FL-83U, 132.5 × 487 × 362.2 mm, 11 kg
TWS FL-12U, 90 × 487 × 362.2 mm

Part numbers

Show all part numbers (3)

TWS-FL, TWS FL-8, TWS FL-1

Request a price and lead time

TWS FL-8 and TWS FL-1 Travelling Wave Fault Locators for Up to 8 Lines. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does installing the locator require a line outage?

No. The unit is connected without taking the line or the substation out of service, and the signal is taken from external line sensors, one per phase.

How many lines can one unit cover?

The TWS FL-1 covers one line, while the TWS FL-8 has between two and eight line boards, expandable in steps of two.

How accurate is the fault location?

The stated accuracy is to within one tower span when GPS synchronisation with 100 ns accuracy is used.