Transformer Valve Coupler, UHF Sensor for Drain Valve Partial Discharge Monitoring
The Transformer Valve Coupler is a UHF partial discharge sensor made to the geometry of each specific transformer. It is inserted into the tank through the drain valve, so UHF monitoring can be added to a transformer already in service without touching the active part.
- Type
- UHF partial discharge sensor
- Application
- partial discharge monitoring of transformers
- Installation
- through the transformer drain valve
- Retrofit method
- non-invasive, on a transformer in service
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Partial discharges in the insulation of a power transformer appear long before a breakdown, and they point to defects in the paper-oil insulation, bushings, leads or poor contacts inside the tank. Recording them in the ultra-high frequency (UHF) band while the transformer is energised lets the development of a defect be followed and repairs planned. The Valve Coupler is used specifically for partial discharge monitoring of transformers.
The sensor picks up the electromagnetic signal of a discharge directly in the oil volume of the tank. The metal tank screens the internal volume from outside interference, so a sensor placed inside receives the discharge signal with less influence from corona and from disturbances generated in the switchgear.
Its distinguishing feature is the method of installation. The sensor is inserted through the transformer's drain valve, so no new holes or flanges are needed on the tank. The manufacturer describes this retrofit as non-invasive: it is carried out on transformers already in service, without opening the tank and without changing the design.
Sensors are designed to the geometry of each transformer, so the design and the length of the part that enters the tank are determined from the data of the specific unit. The item belongs to the group of accessories for partial discharge monitoring and works as part of a measuring chain with an instrument or system that records and analyses the signals. Selection requires the transformer type and rating, a drawing of the tank showing the drain valve position, the type and size of the valve, and details of the instrument or monitoring system to which the sensor will be connected.
Technical specifications
| Type | UHF partial discharge sensor |
|---|---|
| Application | partial discharge monitoring of transformers |
| Installation | through the transformer drain valve |
| Retrofit method | non-invasive, on a transformer in service |
| Design | made to the geometry of the specific transformer |
| Group | accessories for partial discharge monitoring |
Part numbers
Show all part numbers (1)
Valve_Coupler
Request a price and lead time
Transformer Valve Coupler, UHF Sensor for Drain Valve Partial Discharge Monitoring. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the oil have to be drained or the tank opened to fit the sensor?
The sensor is inserted through the drain valve of the transformer. The manufacturer describes the retrofit as non-invasive, with no opening of the tank.
Does one sensor suit any transformer?
No. Sensors are made to the geometry of each transformer, so drawings of the tank and the drain valve data are needed to select one.
Is the sensor a stand-alone instrument?
No. It is an accessory in the measuring chain, and its signal is passed to a partial discharge instrument or monitoring system.