TM8 Nine-Gas Dissolved Gas Monitor for Power Transformer Oil
The TM8 brings laboratory-grade gas chromatography to transformers, measuring nine gases dissolved in the oil. It reports every four hours by default and moves to hourly analysis when concentrations change quickly, with IEC 61850 and DNP3 among its protocols.
- Type
- Online gas chromatography monitor for dissolved gases
- Number of gases
- Nine
- Reporting interval
- Four hours, hourly when rates change quickly
- Protection rating
- NEMA 4X / IP66
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The TM8 is fitted to critical power transformers, including generator step-up units, large transmission transformers and substation or industrial units where the stakes are high. It supplies data for condition-based maintenance, so that decisions about repair or taking a transformer out of service rest on how the gases are changing rather than on a fixed schedule. The measurement itself is made by a built-in gas chromatograph.
The monitor interprets its results through several Duval Triangles, Rogers Ratios, basic gas ratios, total dissolved combustible gas (TDCG) and total hydrocarbons. It checks the accuracy of its measuring system automatically against a calibration gas traceable to NIST standards. Moisture-in-oil, oil temperature and load sensors can be added as options.
The enclosure is NEMA 4X / IP66 and measures 55.9 × 50.8 × 28.4 cm, weighing 29.5 kg. It can sit on a separate pedestal, or be mounted on the transformer tank or a wall. The operating range is -50 to +55°C, with cold start from -20°C, humidity from 5 to 95% without condensation, and storage from -40 to +75°C. Oil inlet pressure is 0 to 3 bar (0 to 45 psi). The monitor works with mineral oil and ester-based insulating fluids.
Communication to SCADA and substation systems runs over RS-232, RS-485, 100Base-FX fibre Ethernet and an internal POTS modem, with copper Ethernet 10/100Base-TX and a cellular modem as options. Supported protocols are ASCII, DNP3, IEC 61850, Modbus RTU, OPC and TCP/IP. The unit has 2 relays for alarms and 3 analogue inputs of 4-20 mA for external sensors. Power is 100 to 240 VAC or 125 to 250 VDC at 50/60 Hz, with a maximum current of 6 A. The monitor can be set up for the condition of the transformer, whether new, stable, degassed or showing unstable gas generation, and includes a standard shutdown procedure, restart after shutdown and manual oil sampling for laboratory DGA.
Technical specifications
| Type | Online gas chromatography monitor for dissolved gases |
|---|---|
| Number of gases | Nine |
| Reporting interval | Four hours, hourly when rates change quickly |
| Protection rating | NEMA 4X / IP66 |
| Dimensions | 55.9 × 50.8 × 28.4 cm |
| Weight | 29.5 kg |
| Mounting | Pedestal, or transformer tank or wall |
| Operating temperature | −50 to +55°C |
| Cold start | −20°C |
| Humidity | 5–95%, non-condensing |
| Storage temperature | −40 to +75°C |
| Oil inlet pressure | 0–3 bar (0–45 psi) |
| Insulating fluids | Mineral oil, ester-based fluids |
| Relays | 2 |
| Analogue inputs | 3, 4–20 mA |
| Interfaces | RS-232, RS-485, 100Base-FX fibre Ethernet, POTS modem |
| Optional interfaces | Cellular modem, 10/100Base-TX copper Ethernet |
| Protocols | ASCII, DNP3, IEC 61850, Modbus RTU, OPC, TCP/IP |
| Power supply | 100–240 VAC or 125–250 VDC, 50/60 Hz, max. 6 A |
Part numbers
Show all part numbers (1)
TM8
Request a price and lead time
TM8 Nine-Gas Dissolved Gas Monitor for Power Transformer Oil. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How often does the monitor analyse the oil?
By default it reports every four hours, and it moves to hourly analysis automatically when gas concentrations change quickly.
Can the monitor connect to SCADA using IEC 61850?
Yes. It supports IEC 61850, DNP3, Modbus RTU, OPC and TCP/IP over RS-232, RS-485 and 100Base-FX fibre Ethernet.
What outdoor conditions does the monitor allow?
An NEMA 4X / IP66 enclosure, an operating range of −50 to +55°C, cold start from −20°C and humidity of 5–95% without condensation.