TM1 Online Dissolved Hydrogen Monitor for Transformer Oil, 20 to 10000 ppm

The TM1 measures the dissolved hydrogen content of transformer oil continuously, showing developing faults between routine oil samples. Its solid-state sensor sits directly in the oil, and the unit needs no membranes, consumables or scheduled sensor replacement.

Model
TM1
DGA method
Solid-state H2 sensor immersed in oil
Hydrogen range
20–10000 ppm
Accuracy
±15% or ±20 ppm

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The monitor is intended for oil-immersed transformers in the 38–138 kV class, particularly in distribution networks where many similar machines are installed. It is fitted to new transformers and to units already in service, as well as to industrial and renewable energy transformers. Hydrogen forms in most tank faults, so its trend reveals a developing fault before it leads to failure.

Measurement is carried out by a solid-state H2 sensor immersed directly in the oil. The sensor measures hydrogen selectively, free from cross-interference by other dissolved gases. Analysis runs every 30 minutes, and data is stored for up to five years. An optional module measures moisture in the oil over the range 0–100 % RS with an accuracy of ±5 %, and oil temperature too.

The hydrogen range is 20–10000 ppm, with an error of ±15 % or ±20 ppm, repeatability of ±5 % or ±10 ppm, and a lower detection limit of 20 ppm. Three 4–20 mA analogue outputs carry the hydrogen level, the rate of change and, optionally, moisture, while two 4–20 mA analogue inputs take signals from other sensors. Three DGA alarm relays and two power and service relays switch up to 3 A at 150 VDC or 300 VAC.

Communication is through RS-232, RS-485 and USB 2.0 ports, using DNP3 and Modbus protocols. Set-up is performed with a configuration program on a PC, and results are reviewed in the TM View software. The monitor is compatible with mineral oil and ester-based insulating liquids.

The unit is mounted permanently on the transformer. The NEMA 4X / IP66 enclosure measures 23.4 × 25.1 × 31.2 cm and weighs 4 kg. Ambient operating temperature runs from −50 to +55 °C, oil temperature from −20 to +105 °C, and oil inlet pressure from 0 to 100 psi (0 to 7 bar). Power is 100–240 V AC, 50/60 Hz, drawing up to 0.8 A. Turnkey installation is available, including training in TM View.

Technical specifications

ModelTM1
DGA methodSolid-state H2 sensor immersed in oil
Hydrogen range20–10000 ppm
Accuracy±15% or ±20 ppm
Repeatability±5% or ±10 ppm
Analysis intervalEvery 30 minutes
Moisture in oil (option)0–100% RS, ±5%
Analogue outputs3 × 4–20 mA
Analogue inputs2 × 4–20 mA
Relays3 DGA alarm relays, 2 power and service relays; 3 A, 150 VDC or 300 VAC
InterfacesRS-232, RS-485, USB 2.0
ProtocolsDNP3, Modbus
Compatible fluidsMineral oil, ester-based liquids
Oil temperature−20…+105 °C
Operating temperature−50…+55 °C
Oil inlet pressure0–100 psi (0–7 bar)
EnclosureNEMA 4X / IP66, 23.4 × 25.1 × 31.2 cm, 4 kg
Power supply100–240 V AC, 50/60 Hz, 0.8 A
StandardsEN 61326-1, IEC 61010-1, IEC 61010-2-81, IEC 60255-21-1, CSA-C22.2 No. 61010-1-04

Part numbers

Show all part numbers (1)

TM1

Request a price and lead time

TM1 Online Dissolved Hydrogen Monitor for Transformer Oil, 20 to 10000 ppm. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does the sensor need replacing or servicing?

The solid-state sensor is immersed in the oil and has no membranes or consumables, and no scheduled sensor replacement is needed.

Which transformers is the TM1 suited to?

Transformers in the 38–138 kV class, oil-immersed with mineral oil or ester-based fluids, both new units and those already in service.

How does the monitor pass data to SCADA?

Through RS-232, RS-485 or USB 2.0 using DNP3 and Modbus, and through three 4–20 mA analogue outputs and alarm relays.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides