T2 Fibre-Optic Transformer Temperature Probe for Windings, -80 to +250 °C
The T2 is an oil-immersed fibre-optic probe for direct measurement of hot spot temperature inside the windings of power transformers and reactors. It covers -80 to +250 °C with a system error of ±1 °C, and dielectric strength above 22000 V/mm at the sensor zone.
- Type
- fibre-optic temperature probe
- Measuring range
- -80 to +250 °C
- System error
- ±1 °C
- Response time
- under 500 ms
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The T2 probe is installed directly in the winding of an oil-immersed power transformer. It is bonded into a standard spacer or fixed at any other point inside the windings. Measuring the hot spot directly gives more accurate readings than a calculation from top oil temperature, and it lowers the risk of damage or unnecessary load restriction. Besides oil-filled transformers, the probe is used in dry-type transformers, reactors, and anywhere strong electromagnetic fields are present, such as switchgear, busbars and tap changers.
The sensing element is a gallium arsenide (GaAs) crystal with a 300 µm sensitive zone. Measurement is contact-based, and the principle needs no recalibration or complicated setup. The glass optical fibre has a 200 µm diameter and a polyimide coating, and the fibres are protected by an inner PTFE tube and a reinforcing helical wrap. A continuous longitudinal slot along the whole length of the cable allows complete oil impregnation.
Probe materials are chosen for dielectric and chemical resistance. The polyimide tube has a dielectric strength above 15000 V/mm, the epoxy joint above 17000 V/mm, and the inner PTFE tube above 18000 V/mm. Dielectric strength is verified to ASTM D149, and the partial discharge level is under 5 pC. The probe withstands factory processes for transformer manufacture, including kerosene desorption and thermal tests, as well as long immersion in oil and vibration. The design suits UHV and HVDC windings.
Probe length is set in steps of 1 m up to 20 m, with options up to 100 m. Mounting discs RD1, RD2 and RD3 of 14.28 mm diameter hold the probe in the winding, and dielectric connectors are also available. The instrument connects through a multimode ST telecom connector. The order code defines the tip type (free or bonded), overall length, length without sheath and disc type.
The probe is compatible with intelligent transformer monitors and with matching optical converters. The installation procedure inside the transformer, the choice of hot spot locations and the number of probes for different winding types are described in the installation manual.
Technical specifications
| Type | fibre-optic temperature probe |
|---|---|
| Measuring range | -80 to +250 °C |
| System error | ±1 °C |
| Response time | under 500 ms |
| Dielectric strength at sensor zone | over 22000 V/mm |
| Partial discharge | under 5 pC |
| Sensing element | GaAs, 300 µm sensitive zone |
| Resistivity | 10⁷ ohm·m |
| Fibre | glass, polyimide coating, 200 µm |
| Materials | epoxy, glass fibre, polyimide, PTFE |
| Chemical resistance | oil, solvents, kerosene |
| Connector | multimode ST telecom |
| Length | steps of 1 m up to 20 m; options up to 100 m |
| Mounting discs | RD1, RD2, RD3 |
| Standards | ASTM D149, ASTM D2413 |
Part numbers
Show all part numbers (11)
T2S-01-RD1-DCT, T2S-01-RD3-DCT, T2S-02-RD1, T2S-02-RD3, T2S-02-01-1, T2S-02-03-1, T2S-06-20-0, T2S-08-RD1, T2S-10-RD3, T2K-06-RD1, T2K-15-01-1
Request a price and lead time
T2 Fibre-Optic Transformer Temperature Probe for Windings, -80 to +250 °C. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the T2 be installed in a dry-type transformer?
Yes. The probe is intended for oil-filled and dry-type power transformers and reactors, and also for switchgear, busbars and tap changers.
Does the probe need periodic recalibration?
No. Measurement on the GaAs crystal needs no recalibration and shows no drift in readings.
How is the probe fixed inside the winding?
It is bonded into a standard spacer, or fixed with mounting discs RD1, RD2 or RD3 of 14.28 mm diameter.
Similar equipment from other manufacturers