T/Guard Link RevB fibre optic hot-spot temperature module, 2 to 8 channels

The T/Guard Link RevB converts signals from fibre optic probes installed in the windings of dry and oil-filled power transformers into 4-20 mA outputs and RS-485 data. It measures -80 to 250 °C with ±1 °C accuracy and runs from a 24 V DC supply.

Number of channels
2, 4, 6 or 8
Measuring range
-80 to 250 °C
Accuracy
±1 °C
Analogue outputs
4-20 mA, one per optical channel

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The T/Guard Link RevB module measures winding hot-spot temperature through fibre optic probes and passes it to control and SCADA systems. It suits transformers of any type, dry or oil-filled, and links the optical probes to the 507 and 509 transformer controllers. Its compact size suits complete supplies from transformer makers.

The module has 2, 4, 6 or 8 optical channels with ST connectors, and each channel has its own 4-20 mA analogue output. The RS-485 serial interface is optically isolated and runs in ASCII or Modbus RTU command mode, in full or half duplex. The mode is switched with a button on the front panel, and an LED shows the active protocol. On Modbus, up to 32 modules can share one bus, which gives a theoretical total of 256 channels. The module has no relays, but its internal temperature sensor can be read through the serial port.

The measuring range is -80 to 250 °C with ±1 °C accuracy. The supply is 24 V DC nominal, with 20–28 V DC acceptable, and consumption is 6 W. The board has a silicone conformal coating to MIL-I-46058C (IPC-CC-830), Type SR.

The housing is cast aluminium with brackets at the corners, and the front membrane is UV-stabilised polyester. Dimensions are 190 × 113 × 38 mm and the weight is 0.7 kg. The module goes in a cabinet protected from rain and dust. It is mechanically fully compatible with the previous T/Guard-Link generation, so replacement needs no change to the mounting. Power, serial and analogue connectors have a 3.5 mm pitch and screw terminals.

Operating temperature is -40 to 72 °C, humidity 5–90% non-condensing, and storage -50 to 80 °C. The module withstands vibration at 80/120 Hz with 0.1 mm displacement and shocks of 10 g half-sine in three planes. EMC tests follow IEC 61000-4-2, -4-3, -4-4, -4-5 and -4-6 and ICES-003. An RS-485 to USB adapter, part number NXP-349, is available for PC setup.

Technical specifications

Number of channels2, 4, 6 or 8
Measuring range-80 to 250 °C
Accuracy±1 °C
Analogue outputs4-20 mA, one per optical channel
InterfaceRS-485 with optical isolation, full or half duplex
ProtocolsASCII or Modbus RTU
Cascadingup to 32 modules on Modbus
Relaysnone
Optical connectorsST
Power supply24 V DC (20–28 V DC)
Consumption6 W
Operating temperature-40 to 72 °C
Storage temperature-50 to 80 °C
Humidity5–90% non-condensing
Vibration and shock80/120 Hz, 0.1 mm; 10 g in three planes
Dimensions190 × 113 × 38 mm
Weight0.7 kg
Housingcast aluminium, UV-stabilised polyester membrane
EMCIEC 61000-4-2, -4-3, -4-4, -4-5, -4-6; ICES-003

Part numbers

Show all part numbers (24)

TGL-02-REVB, TGL-04-REVB, TGL-06-REVB, TGL-08-REVB, TGL-02-REVB-10V, TGL-04-REVB-10V, TGL-06-REVB-10V, TGLB-COM, TGLB-COM-CH2, TGLB-COM-CH4, TGLB-COM-CH6, TGLFL-COM, TGLFL-COM-02, TGLFL-COM-04, TGLFL-COM-06, TGLFL-COM-08, TGL-FL-02-C1, TGL-FL-04-C1, TGL-FL-08-C1, TGL-FL-08-C1_CS-52946, TGL-FL-08-C1_CS-52980, TGL-FL-08-C0, TGL-08-A1-C1, TGL-8-A2-C1

Request a price and lead time

T/Guard Link RevB fibre optic hot-spot temperature module, 2 to 8 channels. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many channels can one system hold?

One module has up to 8 channels, and up to 32 modules can be joined on Modbus, giving a theoretical total of 256 channels.

Can the module replace an older T/Guard-Link unit?

Yes, RevB is mechanically fully compatible with the previous T/Guard-Link and has a similar SCADA interface.

Does the module have relay outputs?

No, there are no relays; temperature is output as 4-20 mA on each channel and over RS-485 in ASCII or Modbus RTU.