International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

SF6GDM Temperature-Compensated SF6 Gas Density Gauge, Up to 3 Contacts

A mechanical local indicator of SF6 gas density in high-voltage equipment that compensates automatically for pressure changes caused by ambient temperature. Optional alarm and lockout contacts are set at the factory to detect gas leakage early.

Type
mechanical SF6 density gauge with temperature compensation
Pressure range
vacuum to 145 psi (-0.1 to 1 MPa)
Indication accuracy
±2 % of maximum scale
Switching accuracy
±3 % of maximum scale

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The gauges are fitted to high and medium voltage SF6 circuit breakers with live-tank and dead-tank designs, to switchgear bushings, to transformers and to gas-insulated switchgear (GIS) in utility and industrial substations. The insulating capability of SF6 depends on the quantity of gas, that is on its density, rather than on its pressure. A conventional pressure switch has to be set to a very low pressure when the temperature falls below 20 °C to avoid false operation, and it detects a gas leak late. A temperature-compensated density gauge does not have this drawback.

Indication accuracy is ±2 % of the maximum scale value for the filling pressure over the whole temperature range, and contact switching accuracy is ±3 % of maximum scale. The pressure range runs from vacuum to 145 psi (from -0.1 to 1 MPa). The instrument is supplied with 0, 1, 2 or 3 instantaneous SPST or SPDT contacts, approved by UL and CSA. Contact ratings are 3 A at 250 V AC, 5 A at 125 V AC, ½ A at 125 V DC and ¼ A at 250 V DC on resistive loads. Surge withstand is 2500 V to ANSI/IEEE C37.90, and dielectric strength is 2000 V AC between contacts and earth for 60 seconds.

The housing, bezel and anti-vibration plate are stainless steel, the terminal box is powder-coated die-cast aluminium, and the lens is polycarbonate stabilised against ultraviolet light. The instrument diameter is 4.25 inch (108 mm) and the dial diameter is 4 inch (101.6 mm). Protection is IP54, corresponding to NEMA 3S. Operating temperature is -40 °C to +70 °C, humidity is 5 to 95 % non-condensing, and the unit withstands vibration at 50/60 Hz with 0.004 inch displacement and 10 g shock. Vibration-damping mounts are supplied as standard.

The standard tank connection is M30 x 2 mm with a sealing ring, and other threads are available on request. Cable entry is through the terminal box with PG16 or M20 cable glands, and mounting is possible from above, below or from the side. Models 38960 differ in scale range and set points. For example, 38960-2 has a scale of 50 to 87 psi abs and set points of 0.45, 0.43 and 0.43 MPa, while 38960-10 and 38960-20 have a scale of 80 to 145 psi abs and set points of 0.72, 0.70 and 0.70 MPa. In 38960-20 and 38960-22 the contacts open, while in the others they close. Every instrument is individually tested before dispatch.

Technical specifications

Typemechanical SF6 density gauge with temperature compensation
Pressure rangevacuum to 145 psi (-0.1 to 1 MPa)
Indication accuracy±2 % of maximum scale
Switching accuracy±3 % of maximum scale
Number of contacts0, 1, 2 or 3
Contact typeinstantaneous SPST or SPDT, UL and CSA
Contact ratings3 A at 250 V AC; 5 A at 125 V AC; ½ A at 125 V DC; ¼ A at 250 V DC
Surge withstand2500 V to ANSI/IEEE C37.90
Dielectric strength2000 V AC, 60 s
Instrument and dial diameter108 mm / 101.6 mm
Materialsstainless steel, die-cast aluminium, polycarbonate
ProtectionIP54 (NEMA 3S)
Operating temperature-40 °C to +70 °C
Humidity5 to 95 % non-condensing
Vibration50/60 Hz, 0.004 inch, shock 10 g
Tank connectionM30 x 2 mm with sealing ring
Cable entryPG16 or M20

Part numbers

Show all part numbers (12)

SF6GDM, 38960-2, 38960-3, 38960-8, 38960-9, 38960-10, 38960-11, 38960-12, 38960-13, 38960-14, 38960-20, 38960-22

Request a price and lead time

SF6GDM Temperature-Compensated SF6 Gas Density Gauge, Up to 3 Contacts. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How does a density gauge differ from a pressure switch for SF6?

It compensates for pressure changes caused by temperature, so it responds to the actual quantity of gas. A pressure switch has to be set to a very low pressure to avoid false signals when the equipment cools.

How many contacts can the instrument have?

0, 1, 2 or 3 SPST or SPDT contacts, with set points configured at the factory to the customer's requirements.

What is the standard tank connection?

An M30 x 2 mm thread with a sealing ring. Other thread sizes are available on request.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides