International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

Passive SAW platform tracking temperature and humidity in switchgear

The platform continuously monitors contact temperature and humidity in medium voltage switchgear, motor control cabinets, busbars, generator circuit breakers and transformers. Passive wireless sensors based on surface acoustic waves (SAW) run without batteries or power cables, and data is collected by the CAM-5 unit.

Temperature range, IS sensor (SAW)
-25 °C to +155 °C
Measurement accuracy, IS sensor (SAW)
±2 °C
Sensor resolution, IS sensor (SAW)
±0.2 °C
Expected service life, IS sensor (SAW)
over 20 years

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The system tracks three main failure mechanisms in power equipment. Thermal breakdown arises from poor connections, incorrectly racked-in breaker trucks and high current loads, and it is detected through contact temperature. Air gap breakdown is linked to moisture, corona and discharges, so humidity and temperature inside cabinets are watched for it. Insulation breakdown is assessed through partial discharges. Continuous condition data helps move maintenance from scheduled repairs to condition-based servicing and reduces unplanned outages.

Temperature sensors are fitted directly at the measurement points on live conductive parts, while air interface antennas are mounted on the switchgear enclosure. The IRM reader serves 12 temperature sensors, 4 antennas and 8 humidity sensors, and passes data to the substation SCADA over Modbus-RTU or to the CAM-5 unit. CAM-5 handles data collection, storage and analytics, plus alarm management, has a local HMI display and connects up to 10 IRM readers, which means up to 200 sensors per site. Communication runs over serial and Ethernet interfaces (copper or fibre) using Modbus, DNP3 and IEC61850.

Intellisaw IS measures conductor temperature on busbars, circuit breaker contacts and medium and low voltage cables, with a BIL rating of up to 185kV. Its range is -25 °C to +155 °C with ±2 °C accuracy and ±0.2 °C resolution, and its expected service life exceeds 20 years. The sensing element is a quartz resonator with no moving parts or electronics. The test voltage under IEC 62271-1 is 95kV/1m plus 185kV impulse, while short-circuit withstand under IEC 62271-200 is 63kA/3s and 171kA peak.

The low profile Intellisaw LP suits places where a bolted IS sensor lacks clearance, such as directly on circuit breaker sleeves. It is rated for operation above 155 °C and does not need a full shutdown for installation. The low voltage CC-TC and CC-WC clip onto a busbar, use iNFC technology, provide electrical insulation up to 1kV and are linked in a chain for hard-to-reach points.

The humidity sensor has a sintered cap, a threaded body, a waterproof M12 connector and 4 kV surge protection, and up to 8 of these sensors can share one CAM-5 bus, for example along a busbar. The Intellisaw TMP and TPD air interfaces are fixed with a magnet or a bolt, have SMA connectors impedance-matched to the IRM48 reader, and fit into tight compartments. The platform meets applicable UL/cUL and IEC requirements.

Technical specifications

Temperature range, IS sensor (SAW)-25 °C to +155 °C
Measurement accuracy, IS sensor (SAW)±2 °C
Sensor resolution, IS sensor (SAW)±0.2 °C
Expected service life, IS sensor (SAW)over 20 years
BIL, IS sensor (SAW)up to 185kV
Test voltage (IEC 62271-1)95kV/1m, 185kV impulse
Short-circuit withstand (IEC 62271-200)63kA/3s, 171kA peak
Operating temperature, LP sensor (SAW)over 155 °C
Electrical insulation (CC)up to 1kV
IRM reader inputs12 temperature sensors, 4 antennas, 8 humidity sensors
IRM readers per CAM-5up to 10
Sensors per siteup to 200
Humidity sensors per CAM-5 busup to 8
Humidity sensor protection4 kV, M12 connector
ProtocolsModbus-RTU, Modbus, DNP3, IEC61850

Part numbers

Show all part numbers (9)

CAM-5, IRM Reader, IRM48, Intellisaw IS, Intellisaw LP, Intellisaw TMP, Intellisaw TPD, CC-TC, CC-WC

Request a price and lead time

Passive SAW platform tracking temperature and humidity in switchgear. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Do the temperature sensors need a power supply?

No. The Intellisaw IS, LP and CC sensors are passive, run without batteries or power cables, and transmit their data wirelessly.

How many measurement points can one system cover?

An IRM reader takes 12 temperature sensors, 4 antennas and 8 humidity sensors, and the CAM-5 unit connects up to 10 readers and up to 200 sensors per site.

How is the system connected to SCADA?

The IRM reader connects to SCADA directly over Modbus-RTU, while the CAM-5 unit passes data on through Modbus, DNP3 or IEC61850 over serial and Ethernet interfaces.