QTMS modular transformer monitoring system, up to 14 modules and 6 bushings
The QTMS is a scalable monitoring system for power transformers, configured for a particular machine or standardised across a whole fleet. It has up to 14 modules with analogue and digital inputs, direct winding temperature measurement through fibre optics, and monitoring of up to 6 bushings.
- Modules
- from 1 to 14
- Bushing monitoring
- up to 6 (minimum 3 signals)
- Analogue inputs
- up to 8 parameters
- Digital inputs
- up to 14, optically isolated, up to 250 V DC, threshold above 75 V DC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The system runs from 120–240 V AC ±20 %, 50/60 Hz, or 125–250 V DC ±15 %, and draws less than 50 W. It operates from −40 to +72 °C (the bushing module from −20 to +72 °C) at 5–95 % humidity, non-condensing, and the enclosure is IP20, with a higher rating on request. Tests follow IEC 60255, IEEE C37.90, IEC 61000-4, EN 55011 Class A and IEC 60068-2.
Between 1 and 14 modules are combined to suit the site and its sensors. The processor module, with a dual-core TX6-DL processor, offers Ethernet 10/100 TX (RJ45), USB-A, 4-wire RS-485 and a remote display port, plus an optional Ethernet FX port with an ST connector and a system status relay. The serial port supports DNP 3.0 (Level 3), Modbus and IEC 60870-5-104, IEC 61850 runs over Ethernet, and the user interface is web-based.
The analogue module measures up to 8 parameters: Pt100 thermometers from −40 to 120 °C for oil and air and from −40 to 200 °C for calculated winding temperature; current through clamp-on transformers of 0–5, 10, 20 or 100 A; current loops of 0–1 and 4–20 mA; 0–100 mV and 0–10 V DC; 0–140 or 0–320 V AC at 50/60 Hz; and potentiometers of 1500–15000 Ω. Tap changer position comes from current loops, 40–2500 Ω resistor bridges or voltage. The digital module offers up to 14 optically isolated inputs, a threshold above 75 V and a maximum of 250 V DC. Up to 8 fibre optic probes read winding temperature to ±1 °C.
The bushing module takes signals from 3 to 6 bushings (leakage current, temperature and reference voltage) and calculates the phase difference between leakage current and reference voltage. Accuracy is better than ±0.0001 for tan δ (a 0.1 mrad phase shift), 0.2 % for capacitance and ±0.1 % for leakage current and reference voltage. One partial discharge OCU connects through Ethernet. The output module has 8 Form C relays rated 10 A at 120/240 V AC and 10 A at 30 V DC, plus 2 analogue loops of 0–1 mA or 4–20 mA. The log keeps 100 variables at intervals from 1 minute to 24 hours, and 32 parameters recorded every 15 s for 90 days without overwriting, in 4 GB. An optional 2 x 16 character backlit LCD with 8 navigation, test and reset buttons is available.
Technical specifications
| Modules | from 1 to 14 |
|---|---|
| Bushing monitoring | up to 6 (minimum 3 signals) |
| Analogue inputs | up to 8 parameters |
| Digital inputs | up to 14, optically isolated, up to 250 V DC, threshold above 75 V DC |
| Fibre optic inputs | up to 8, ±1 °C error |
| Oil and air temperature | −40…120 °C (Pt100) |
| Winding temperature | −40…200 °C |
| Output relays | 8 Form C, 10 A at 120/240 V AC, 10 A at 30 V DC |
| tan δ error | better than ±0.0001 (0.1 mrad) |
| Capacitance error | better than 0.2 % |
| Processor | dual-core TX6-DL |
| Interfaces | Ethernet 10/100 TX (RJ45), Ethernet FX (ST), USB-A, RS-485 |
| Protocols | IEC 61850, DNP 3.0 (Level 3), Modbus, IEC 60870-5-104 |
| Data log | 100 variables, 32 parameters every 15 s for 90 days, 4 GB |
| Power supply | 120–240 V AC ±20 %, 125–250 V DC ±15 %, <50 W |
| Operating temperature | −40…+72 °C |
| Humidity | 5–95 % non-condensing |
| Protection rating | IP20 |
Part numbers
Show all part numbers (10)
QTMS-00258768, QTMS-00402693, QTMS-00408449, QTMS-00273414, QTMS-00404337, QTMS-00408478, QTMS-00302705, QTMS-00413278, QTMS-00423224, QTMS-00426301
Request a price and lead time
QTMS modular transformer monitoring system, up to 14 modules and 6 bushings. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many bushings can the QTMS monitor?
Up to 6 bushings, with at least 3 signals required, and a tan δ error better than ±0.0001.
Which protocols does the system support for SCADA?
IEC 61850, DNP 3.0 (Level 3), Modbus and IEC 60870-5-104, over Ethernet or the RS-485 serial port.
How long is data kept without overwriting?
32 parameters recorded every 15 seconds are kept for 90 days in 4 GB of memory.
Similar equipment from other manufacturers