International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

QCM-PPDM Portable Monitor for Partial Discharge in Transformers and GIS, 3 or 6 UHF Channels

QCM-PPDM is a self-contained portable system for fast partial discharge checks and analysis in gas insulated switchgear and power transformers. It runs in the field through a touch screen and needs no fixed monitoring infrastructure.

Type
Portable partial discharge monitor
Inputs
3 or 6 UHF channels plus 1 noise antenna channel
Frequency band
300 to 1500 MHz
Sensitivity
More than 6 mm, less than 5 pC

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The instrument is used for scheduled checks of partial discharge, both online and offline, on high-voltage insulation in GIS and in power transformers at transmission substations, power plants and large industrial sites. It also serves during installation and commissioning of GIS and transformers, for quality testing during or after assembly or manufacture, and in laboratories that measure partial discharge in any insulating material. The results form the basis for maintenance according to condition.

The system detects, characterises and locates partial discharge defects, so their danger can be judged and repairs planned. The instrument is also suitable for HVDC equipment. Signals are taken from UHF sensors in the band from 300 to 1500 MHz, and the sensitivity is stated in the documentation as more than 6 mm and less than 5 pC. The sensors are mounted either inside or outside the equipment.

The instrument is made in two versions, with 3 UHF channels or with 6 UHF channels, and each has an extra channel for a noise antenna. The sampling rate is 15.4 kS/s per channel, or 107.5 kS/s in total across 7 channels sampled simultaneously. It has time synchronisation and coincidence filters to remove noise. Partial discharge alarms, warnings and system status are shown on the screen, and reports can be configured. The system covers more than 100 monitoring points and can be expanded on site without reconfiguration.

Control is through a 12 inch touch screen (1024 x 768) with a rotary and push-button control. The processor runs at 1.2 GHz, with 1 GB of memory and 16 GB of data storage. Connections are an external Ethernet RJ45 port (10/100 Mbit/s), a USB port for firmware and configuration upgrades and manual data download, and GPRS as an option. The supply is universal, 90 to 264 V AC at 47 to 63 Hz or 40 to 290 V DC, with a power of 70 W and a current of 110 mA at 230 V AC. The enclosure is IP66, measures 508 x 355 x 254 mm and weighs 17 kg.

The operating temperature range is -25 °C to +55 °C, storage is -25 °C to +75 °C and humidity is 5% to 95% non-condensing. The instrument suits surveys lasting from 24 hours to 12 months. Its tests cover seismic performance to IEEE C37.98, climatic tests to BS EN 60068-2-2 and related parts, and EMC to BS EN 55022, the BS EN 61000 series, IEC 60255-5 and IEC 61180-1.

Technical specifications

TypePortable partial discharge monitor
Inputs3 or 6 UHF channels plus 1 noise antenna channel
Frequency band300 to 1500 MHz
SensitivityMore than 6 mm, less than 5 pC
Sampling15.4 kS/s per channel; 107.5 kS/s across 7 channels
Monitoring points100+
Processor1.2 GHz
Memory / storage1 GB / 16 GB
InterfacesEthernet RJ45 10/100 Mbit/s, USB, GPRS optional
Display12 inch touch screen, 1024 x 768
Power supply90 to 264 V AC, 47 to 63 Hz; 40 to 290 V DC
Power consumption70 W; 110 mA at 230 V AC
Operating temperature-25 °C to +55 °C
Storage temperature-25 °C to +75 °C
Humidity5% to 95% non-condensing
Ingress protectionIP66
Dimensions508 x 355 x 254 mm
Weight17 kg
StandardsIEEE C37.98, BS EN 60068-2-2, BS EN 55022, IEC 60255-5, IEC 61180-1

Part numbers

Show all part numbers (2)

QPPDM, QCM-PPDM

Request a price and lead time

QCM-PPDM Portable Monitor for Partial Discharge in Transformers and GIS, 3 or 6 UHF Channels. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How do the instrument versions differ?

By the number of UHF measurement channels, which is 3 or 6, and each version has one additional channel for a noise antenna.

Can the instrument stay at a substation for long-term monitoring?

Yes, it is designed for surveys lasting from 24 hours to 12 months, and the enclosure is protected to IP66.

Which mains supply does the instrument run from?

The universal supply accepts 90 to 264 V AC at 47 to 63 Hz, or 40 to 290 V DC.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides