QBCM Circuit Breaker Condition Monitoring System, LT, ST and IP Versions

The QBCM records the parameters of every high voltage circuit breaker operation and builds condition trends over time, covering coil currents and voltages, phase currents, pressure, SF6 density and humidity, and the state of batteries, motors and heaters. New operations are automatically compared with a reference waveform, and deviations raise warnings.

Versions
QBCM-LT, QBCM-ST, QBCM-IP
Power supply
100–240 V AC (50/60 Hz), 110–250 V DC
Phase currents
3 channels, 0-1 V AC or 0-333 mV AC, split-core CTs
Closing coils
1–3 channels, 0-1 V DC, shunt or Hall sensor

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The system is applied in condition-based maintenance programmes for group-operated (GOB) and independent-pole-operated (IPOB) breakers, as well as SF6, dead-tank and live-tank breakers. Monitoring while the equipment is energised reduces the need for offline testing, and it supplies data for planning the replacement of old breakers across large fleets.

The QBCM-LT gives basic monitoring for group-operated breakers, covering coil currents and voltages, phase currents, cabinet temperature, pressure, SF6 density and humidity, battery voltage and digital inputs. The QBCM-ST adds monitoring of heaters, the motor and the battery bank, while the QBCM-IP covers the full set of functions for independent-pole breakers. A travel transducer is optional and records the contact travel curve.

The fingerprint function compares each operation with a chosen reference and shows both the change and the rate at which the condition is changing. The configuration of one breaker can be cloned to similar units, and the cloned setup shortens installation, which is stated to take under one day. SF6 prediction algorithms give accuracy of ±1 day. Storage on an 8 GB microSDHC card holds up to 10000 operations with full waveforms at 32, 64 or 128 samples per period.

Coil currents are measured with shunts or Hall sensors, while phase and heater currents are measured with split-core current transformers. Digital inputs are rated up to 250 V DC with a minimum of 80 V. Three relay outputs, for monitor fault, breaker fault and a programmable warning, have dry contacts rated 5 A at 125 V AC, 3 A at 250 V AC and 0.1 A at 250 V DC.

Access is through a web interface and remote client software, with HTTPS support and 256-bit encryption, and COMTRADE files from offline test data can be imported. The unit speaks DNP3.0, IEC 61850 and Modbus, and time sync is by NTP or IEEE 1588 PTP. It is mounted in the breaker control cabinet (IP20) or in an optional IP67 outdoor enclosure. Operating temperature is -40 to +75 °C, with a power supply of 100–240 V AC or 110–250 V DC.

Technical specifications

VersionsQBCM-LT, QBCM-ST, QBCM-IP
Power supply100–240 V AC (50/60 Hz), 110–250 V DC
Phase currents3 channels, 0-1 V AC or 0-333 mV AC, split-core CTs
Closing coils1–3 channels, 0-1 V DC, shunt or Hall sensor
Tripping and backup coils2–6 channels, 0-1 V DC, shunt or Hall sensor
Battery voltage2 inputs up to 299 V DC
SF6 density, pressure, humidity1–3 channels 4–20 mA or 1 RS 485 channel (Modbus)
Digital inputsUp to 250 V DC, minimum 80 V
Resolution32 / 64 / 128 samples per period
MemorymicroSDHC 8 GB, up to 10000 operations
ProtocolsDNP3.0, IEC 61850, Modbus
Time synchronisationNTP or IEEE 1588 PTP
Relays3 × dry contact 5 A at 125 V AC, 3 A at 250 V AC, 0.1 A at 250 V DC
Operating temperature-40…+75 °C
Storage temperature-60…+75 °C
Humidity5–97% non-condensing
Enclosure ratingIP20 (in breaker cabinet), IP67 option
Dimensions and weightLT 381 × 140 × 70 mm, 1.50 kg; ST 381 × 140 × 89 mm, 1.93 kg; IP 381 × 140 × 115 mm, 2.24 kg
EMC and safety standardsEN61000-6-5, EN55011 Class A, IEC60255-27, IEC 60255-21-1, -2

Part numbers

Show all part numbers (4)

QBCM, QBCM-LT, QBCM-ST, QBCM-IP

Request a price and lead time

QBCM Circuit Breaker Condition Monitoring System, LT, ST and IP Versions. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How do the LT, ST and IP versions differ?

LT gives basic monitoring for group-operated breakers, ST adds monitoring of heaters, motor and battery, and IP covers the full set of functions for independent-pole breakers.

How many operations does the monitor store?

Up to 10000 operations with full waveforms on an 8 GB microSDHC card.

Which protocols are supported for integration with substation systems?

DNP3.0, IEC 61850 and Modbus, with time synchronisation via NTP or IEEE 1588 PTP.