PPS2 supply unit for PD monitoring on HV cables, up to 60 W from line current

The PPS2 powers PD detectors fitted to high voltage cables where no low voltage mains supply exists on site. It draws energy directly from the monitored line through toroidal transformers fixed around the cable, and delivers up to 60 W at 24 V DC.

Maximum output power
60 W with 3 toroids at most
Scalable output power
one, two or three toroids
Output voltage
24 V DC, tolerance ±5%
Output current
2.5 A at most

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The PPS2 supports continuous partial discharge monitoring at high voltage cable joints in manholes and vaults, at joints inside cable tunnels, and at outdoor cable terminations. Such locations usually have no low voltage supply for monitoring equipment, so the energy is taken from the cable itself while it carries load.

The unit has two main parts: a removable toroidal transformer that surrounds the cable, and an electronic regulated power supply block. Between one and three toroids can be used, depending on the power required. The maximum output is 60 W at 24 V DC, tolerance ±5%, with a current of 2.5 A at most. Supply starts when the cable is live and its current is high enough: at least 250 A in a single phase cable, or 110 A per phase in a three phase cable, for 10 W; and 480 A or 200 A per phase for 20 W.

A Power Good signal, an open collector output, lets the monitoring system check that its electronics have adequate power. A 15 Vp/p square wave synchronisation signal on a BNC connector helps identify PD during post processing, and its phase shift against the primary current is 6° ±5°.

The PPS2 withstands fault conditions on the high voltage line, including temporary overload and short circuit. An internal detection and self limiting circuit keeps the supply and connected equipment working, and short circuit protection is built into the electronic unit.

Toroids fit cables of 70 to 180 mm diameter. Dimensions are Φ370 mm x 75 mm without the IP68 cover and Φ400 mm x 100 mm with it, each weighing about 5 kg, and they connect through three removable screw terminals. The electronic unit is linked to the toroids by a 10 m cable. Installation is possible where the cable is not fully buried, such as in a tunnel or in chambers and pits with access to the cable section.

Technical specifications

Maximum output power60 W with 3 toroids at most
Scalable output powerone, two or three toroids
Output voltage24 V DC, tolerance ±5%
Output current2.5 A at most
Power Good signalopen collector, <24 Vdc, <20 mA
Synchronisation signal15 Vp/p, square wave
Sync phase shift against primary current6°±5°
Cable current0 ÷ 2 kA (per phase)
Minimum cable current at Pout=10 W250 A (1 phase) / 110 A per phase (3 phase)
Minimum cable current at Pout=20 W480 A (1 phase) / 200 A per phase (3 phase)
HV cable diameter70–180 mm
Toroid dimensionsΦ370 mm x 75 mm (without IP68 cover), Φ400 mm x 100 mm (with IP68 cover)
Toroid weightabout 5 kg
Toroid connection3 removable screw terminals
Cable between toroid and electronic unit10 m
Synchronisation connectorBNC
IndicatorsLED Power Good, LED Line
Protection degreeup to IP68 (on request)

Part numbers

Show all part numbers (1)

PPS2

Request a price and lead time

PPS2 supply unit for PD monitoring on HV cables, up to 60 W from line current. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What minimum cable current does the PPS2 need to run?

For 10 W at the output, at least 250 A in a single phase cable or 110 A per phase in a three phase cable; for 20 W, 480 A or 200 A per phase.

Which cable diameters does the toroid fit?

Toroidal transformers fit cables from 70 to 180 mm in diameter.

What happens to the supply during a short circuit on the line?

An internal detection and self limiting circuit protects the PPS2 and connected equipment during overload and short circuit on the HV line.