PPM-97 corona probe for partial discharge in motor and generator stators, 0.5–10 MHz
The PPM-97 is a battery-powered portable instrument for offline detection of partial discharge in the stator windings of rotating machines. Its ferrite probe pinpoints discharge activity to a particular slot and to a position along the active iron.
- Type
- Portable corona probe, offline partial discharge locator
- Applies to
- hydro and turbo generators, large AC motors
- Frequency band
- 0.5–10 MHz
- Current ranges
- 10 / 30 / 100 / 300 / 1000 mA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Partial discharge activity inside stator insulation is the target of this test. The probe is applied to hydro generators, turbogenerators and large synchronous and asynchronous AC motors, including machines with resin-rich or VPI insulation. The method is recommended in IEEE Standard 1434, and it shows the exact location of discharge activity within the slot portion of the winding.
Testing is carried out on a machine taken out of service. Each phase winding is energised in turn from an external high-voltage AC source, while the operator moves the probe along the stator slots. The instrument complements online partial discharge monitoring: the online system shows whether discharges are present and at what level, and the probe narrows them down to a slot and position. Where no other partial discharge data exist, the probe can serve as a standalone test for locating active zones.
The probe also checks the bond between layers of main insulation in the slot portion of new coils and bars with resin-rich insulation or individual VPI impregnation, and the slot fill with resin in windings with global VPI impregnation. It is therefore used when new windings are accepted, at commissioning and during repairs.
The meter is tuned to partial discharge frequencies with a 0.5–10 MHz band. Current ranges are 10, 30, 100, 300 and 1000 mA, with peak and battery-check modes. Sensitivity to a continuous signal is 0.9 V RMS. The meter input is a BNC connector, and earthing uses a metal clamp with 5 attachment methods. The meter measures 9 x 15.5 x 4.5 cm and weighs 445 g, and the probe is 91 cm long. It runs on 2 batteries of 9 V.
The kit includes the probe with its peak pulse meter, an earthing lead, a carrying case and the operating manual. Versions with different probe lengths and tip configurations are available.
Technical specifications
| Type | Portable corona probe, offline partial discharge locator |
|---|---|
| Applies to | hydro and turbo generators, large AC motors |
| Frequency band | 0.5–10 MHz |
| Current ranges | 10 / 30 / 100 / 300 / 1000 mA |
| Modes | peak, battery check |
| Sensitivity to continuous signal | 0.9 V RMS |
| Input | BNC connector |
| Earthing | metal clamp with 5 attachment methods |
| Meter dimensions | 9 x 15.5 x 4.5 cm |
| Meter weight | 445 g |
| Probe length | 91 cm |
| Power supply | 2 x 9 V batteries |
| Standard | IEEE Standard 1434 |
Part numbers
Show all part numbers (1)
PPM-97
Request a price and lead time
PPM-97 corona probe for partial discharge in motor and generator stators, 0.5–10 MHz. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the probe be used on a machine under load?
No. It is an offline instrument, because each stator winding phase is energised from an external high-voltage AC source.
How does the probe complement online partial discharge monitoring?
Online monitoring shows whether discharges are present, while the probe locates them to a specific slot and position in the active iron.
Is the probe suitable for checking new VPI windings?
Yes, it checks the bond between layers of insulation in resin-rich and VPI coils and bars, and the slot fill with resin in windings with global VPI impregnation.